SIL-2 features
This appendix details the special conditions to comply with the requirements of EN 61508
for SIL-2.
The Rosemount 935 open path combustible gas detector can be used in low and high
demand mode applications. See IEC 61508-4:2010, Chapter 3.5.16.
E.1

Safety relevant parameters

Type: B
Structure: 1oo1
HFT: 0
Mean time to repair: 72 hours
Ambient temperature: maximum 149 °F (65 °C)
Proof test interval: 52 weeks (1 year)
λ
= 2056.1 fit
S
λ
= 1976.1 fit
D
λ
= 114.8 fit
DU
λ
= 1933.4 fit
SD
λ
= 1861.4 fit
DD
SFF = 97%
PFD
avg
PFH = 1.15 x 10
E.2

General conditions for safe use

The Rosemount 935 should consist only of the approved hardware and software
models.
Consider the application advice and limitations of the Manual. For calibration and
maintenance, consider the regional and national regulations.
The 24 V power supply must fulfill the requirements for PELV/SELV of EN 60950.
The HART
safety related data.
The alert conditions according to SIL-2 can be implemented by an alert signal via the
20 mA current loop.
After installation and configuration, the operator must verify the set-up parameters
and check the function of the Rosemount 935.
Rosemount 935
-4
= 6.45 x 10
-7
1/h
®
and RS-485 interfaces are not allowed to be used for the transmission of
DC = 94%
PFD
= 6.4%
%_SIL2
PFH
- 11.5%
%_SIL2