Page 1
US 6,747,573, US 7,019,241 EnOcean GmbH Phone +49.89.67 34 689-0 Subject to modifications Kolpingring 18a +49.89.67 34 689-50 TCM 300 / 300C / 320 / 320C User Manual V1.25 82041 Oberhaching info@enocean.com June 14, 2011 4:53 PM Germany www.enocean.com Page 1/52 Downloaded from Elcodis.com...
Page 2
This information describes the type of component and shall not be considered as assured characteris- tics. No responsibility is assumed for possible omissions or inaccuracies. Circuitry and specifications are subject to change without notice. For the latest product specifications, refer to the EnOcean web- site: http://www.enocean.com.
PROG_EN RVDD The figure above shows the pin out of the TCM 300 / TCM 320 hardware. The pins are named according to the naming of the EO3000I chip to simplify usage of the DOLPHIN API. The table in section 2.2 shows the translation of hardware pins to a naming that fits the functionality of the built-in firmware.
TCM 300 / 300C / 320 / 320C Repeater configuration TCM 3x0 provides the option to activate a one or two-level repeater for EnOcean radio tele- grams. 1-level repeater: If a received telegram is a valid and original (not yet repeated), the tele- gram is repeated after a random delay.
2.10 Smart Acknowledge TCM 3x0 provides a post master function with 15 mail boxes for systems using EnOcean smart acknowledge technology. This functionality is switched on in all operating modes. For detailed information on smart acknowledge please refer to the Smart Acknowledge sys- tem specification.
TCM 300 has to be soldered according to IPC/JEDEC J-STD-020C standard. TCM 300 shall be handled according to Moisture Sensitivity Level MSL4 which means a floor time of 72 h. TCM 300 may be soldered only once, since one time is already consumed at production of the module itself.
EN60669-2-1). As soon as the supply voltage drops below the VON threshold level the current consumption is reduced. TCM 300 will enter standby sleep mode (worst case 35 µA), TCM 320 will enter short term sleep mode (1.8 mA) for 200 ms. As long as the voltage at VDD does not drop below VOFF during that phase the module will restore the output state as set before the voltage dip.
Page 39
TCM 300 / 300C / 320 / 320C OEM Requirements In order to use EnOcean’s FCC ID number, the OEM must ensure that the following condi- tions are met: End users of products, which contain the module, must not have the ability to alter the firmware that governs the operation of the module.
TCM 300 / 300C / 320 / 320C IC (Industry Canada) Certification In order to use EnOcean’s IC number, the OEM must ensure that the following conditions are met: Labeling requirements for Industry Canada are similar to those required by the FCC.
Alliance pursues standardization of communication profiles, ensuring that sensors from one manufacturer can communicate with receiver gateways of another, for example. End-users thus have the entire product portfolio - enabled by EnOcean - at their disposal. And product manufacturers can focus on their own special field.
A.3.1 ID Range commands Every TCM 300 supports a unique 32 bit ID and in addition a range of 128 IDs starting at an BaseID address. At production, every TCM 300 is programmed with a unique ID and a BaseID address.
Need help?
Do you have a question about the TCM 300 and is the answer not in the manual?
Questions and answers