8.1.2.3 LCD Screen Test
Perform the following steps to run the LCD Screen Test:
1. In the RUN TEST screen, tap LCD TEST.
2. A screen opens to show the five different colours like red, green, blue, white and black.
3. Either after the test is complete or in between the test, tap anywhere on the screen to come out of the LCD Screen Test.
8.2 Alarm Count & Voltages
Fig. 41: Alarm Count & Voltages
NS-MN-0032 / 11.2020
The ALARM COUNT & VOLTAGES tab displays a number of voltage values and analogue values
(relevant to access level 3 use).
Signal
Description
Measurement of the PSU DC supply
DC voltage
Voltage
Measurement of the Charger Output
Charger
Voltage
1
Battery voltage
Measurement of the Battery Voltage
Measurement of the battery wiring
Battery wiring
resistance
1
Monitored input 1 Measurement of the input signal condition
Panel MCP
Measurement of the input signal condition
Measurement of the earth condition for the
Earth (System)
main PCBA board (includes loop 1)
Measurement of the earth condition for
Earth (Loop 2)
loop 2
Measurement readings are shown for indicative purposes only.
1
The measurement reading depends also on battery capacity and condition.
2
The measurement reading depends also on DC voltage, battery condition and the earth condition.
An
indication is displayed when the reading is outside the normal range.
User's Guide SMX-AUS
Normal / Range
Units
24
(22.7 – 25.0)
Volts
28
(29 – 25)
Volts
27.4 (27.9 – 21.5)
Volts
427 (300 – 600)
mOhms
2
2064 (1067 – 3025)
count
2
3312 (1235 – 3661)
count
858 (496 - 1985)
count
858 (496 - 1985)
count
37