Routing Of Control Wiring To Afdh Cabinet; Control Wiring Connections (Tracer® Adaptiview™ Model Afdh Only) - Trane CVHE Installation Instructions Manual

E-frame upgrade adaptive frequency drive for tracer adaptiview centrifugal chiller controllers
Table of Contents

Advertisement

Routing of Control Wiring to
AFDH Cabinet
NOTICE
Route Incoming Power Conduit to the
Roof of the AFDH Cabinet!
Routing the incoming power conduit into the AFDH
cabinet anywhere other than through the specified
location on the cabinet roof, will be considered an
unsupported field modification to the cabinet design.
The air-cooled AFDH drive is designed to have the
incoming power conduit routed vertically into the unit
through the removable conduit connection cover
located on the left-hand rear corner of the cabinet roof.
If the starter that is being replaced by the AFDH drive
has the incoming power conduit routed horizontally
across the top of the starter, or connected to the side or
to the bottom of the starter cabinet, an electrician will
be required to reconfigure the conduit and wiring.
Figure 42. Wiring connections to 2X1 terminal strip in AFDH
4
5
6
7
3
8
9
10
11
12
13
AFDH-SVN004C-EN
1A
2A
4B
9A
10A
3D
4C
Keep Dirt, Debris, or Metal Filings From
Entering the Drive Cabinet!
Failure to observe the appropriate precautions could
result in damage to the electrical components when
they are energized for the first time. Take all precautions
necessary to prevent any dirt, debris, or metal filings
from entering into the drive cabinet during the
installation process.
Control Wiring Connections
(Tracer® AdaptiView™ Model
AFDH Only)
1
2
2X1
2X2
Installation
NOTICE
203A
203B
207A
207B
205A
208A
209A
401B
402B
410A
411A
412A
49

Advertisement

Table of Contents
loading

This manual is also suitable for:

CvhfAfdh