Troubleshooting - GE Match lite 500 User Manual

Table of Contents

Advertisement

g
Whenever a malfunction occurs, first check external factors (e.g connections, temperature, humidity or
load) to determine whether the problem is caused by the unit itself or by its environment. Subsequently
check the input fuse: it may be blown. If so: replace the fuse (see 5.2) and be sure that the UPS is not
overloaded.
The following chart is a simple troubleshooting checklist only. If the suggested solution does not succeed,
or if the information is insufficient to solve the problem, please contact your dealer or consult
www.gedigitalenergy.com.
PROBLEM
Blown input fuse
No output voltage during self
test (3.2.2)
Only battery start possible,
LED 'LINE' blinks
UPS will not switch on,
LED 'LINE' blinks
UPS will not switch on nor off
UPS will not switch on, LEDs
'LINE' and 'BAT' blink
UPS operates on battery
though mains is present
Continuously sounding buzzer
mains present
Continuously sounding buzzer
mains not present
UPS does not provide the
expected back-up time, no
alarm 'replace battery'
Blinking LED 'BAT',
intermitting buzzer
OPM_MAE_LTE_500_XXX_1GB_V040

6 - Troubleshooting

POSSIBLE CAUSE
Output overload
System failure
System failure
Blown input fuse
UPS is in programmed
shutdown mode
Computer interface problem
Software configuration error
Blown input fuse
Very high, low or distorted
mains voltage
UPS overload
UPS overload or short circuited
in battery mode
Weak battery: recent outage or
worn out battery
Quick Battery Test just after
installation or mains failure
Weak battery
7
GE Digital Energy
SOLUTION
Reduce load, replace fuse
Please contact your dealer or
consult www.gedigitalenergy.com
Please contact your dealer or
consult www.gedigitalenergy.com
See above
Normal situation
Disconnect interface. If this solves
the problem, check interface cable
and attached computer.
Disconnect mains, press 'OFF'
during 2 seconds to reset the
internal processor.
See above
Check mains voltage, contact
qualified electrician
Reduce load
Disconnect mains, press 'OFF'
during 2 seconds to reset the
internal processor.
Charge the battery. If the battery is
near the end of its service life,
consider replacing the battery even
if the 'replace battery' alarm is not
yet active.
Allow the UPS to recharge the
batteries
Read 5.3
Match lite 500: user manual 4.0 (GB)