MDT Technologies SCN-RTRGW.02 Technical Manual page 71

Glass room temperature controller smart
Table of Contents

Advertisement

Technical Manual
Glass Room Temperature Controller Smart
Behaviour on reset
The following parameter defines the behaviour at the initialization of the device:
Figure 34: Ventilation control – Behaviour on reset
"Behaviour on reset" defines the level to be called after a reset if the controller has no value yet.
This can be "automatic mode" or "Levels 0 – 4".
Sticking protection
The following parameter activates a sticking protection:
Figure 35: Ventilation control – Sticking protection
To protect the ventilation from getting stuck, a sticking protection can be activated. This lets the
ventilation run briefly at the highest level if it has not been moved for 24 hours (= level 0).
Priority
The priority can call a certain state:
Figure 36: Ventilation control – Priority
When the polarity is set (value = 1), the set state is called up. With "Value 0" the priority is taken
back again.
The following table shows the communication objects for priority control:
Number
Name/Function
44
Ventilation control – Object priority
Table 75: Communication object – Ventilation control: Priority
MDT technologies GmbH • 51766 Engelskirchen • Papiermühle 1 • Germany
71
Phone: +49-2263-880 • knx@mdt.de • www.mdt.de
SCN-RTRGx.02
Length
Usage
1 Bit
Value 1 calls the adjusted level