Iobus Cable And Shunt/Jumper Connections - Siemens APACS+ Installation And Service Instruction

Remote i/o rack
Hide thumbs Also See for APACS+:
Table of Contents

Advertisement

SD39RIO-1
APACS+ and QUADLOG hardware is certified to meet certain safety agency
(EMC, CSA) vibration, and temperature standards. To ensure that test certifications
are not violated, note the following:
ESD covers and dust covers on unused connectors must be attached at all times.
Cables must be secured at all times by screwlock mechanisms.
No unauthorized modifications are allowed to APACS+ or QUADLOG products.

2.5 IOBUS Cable and Shunt/Jumper Connections

The IOBUS is redundant (sides A and B) and can have a maximum capacity of 40 nodes defined as one
control module and up to 39 I/O modules. The actual nodal capacity depends upon the type of rack used or
the combination of racks used (see section 2.2.2).
A minimum node IOBUS consists of two modules: a control module and an I/O module; however, the control
module must reside in a SIXRAC or a MODULRAC to communicate over the MODULBUS (M-BUS). The
IOBUS capacity of a Remote I/O Rack is fixed at four modules (nodes) and cannot be configured into
separate segments; however, the Remote I/O Rack's IOBUS can continue into other Remote I/O Racks,
SIXRACs, MODULRACs, or UNIRACs. IOBUS cables and shunts (see Figures 2-6 through 2-10) are used
to establish the physical length of an IOBUS.
January 2001
Figure 2-5 Cable Tie Points for Strain Relief
IMPORTANT
INSTALLATION
2-9