Page 1
CR00343 178 070 63-4 2022-04-01 Providing sustainable energy solutions worldwide Installation and maintenance instruction B 70i-3R FAME/RME J/K LMV37 E6NC Translation of the original instructions.
Page 2
1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\download 2. www.bentone.com\download nedladdning or scan QR-code. eller scan QR-koden. eller scanna QR-koden.
• Make sure when installing the burner that there is enough space to service the burner. • The electrical installation must be professionally carried out in accordance with applicable high voltage regulations. • Make sure that the burner is suitable for the application (see Technical Data). 165 105 01-2 2021-12-07 Bentone...
Page 5
• When in operation, the burner’s noise level can exceed 85 dBA – use hearing protection! - Operation: • Carry out all stipulated settings, service and inspection work within the set time. • If the oil burner control has a solid red light, contact your installer. Bentone...
• Annual cleaning and checking for the presence of water in the tank should be done to avoid corrosion and microorganisms. 165 405 06 2021-12-07 Bentone...
Ø C *Minimum recommended floor dimensions. 2.2 Electrical Specifications The burner corresponds to IP 54 Type Motor Operating supply Sound 230/400V, 10.4/6.0A 230V, 0.7A, 50Hz 89dBA ± 0.5dBA B 70i-3R Max operating current, see data plate 165 105 79-2 Bentone...
Basic settings should only be seen as setting values to get burner to start. Once the burner has started and established flame, it is necessary to adjust the settings so that they are adapted to the installation and the fuel used. Air settings Nozzle assembly Scale 1000 1200 1400 1600 Burner output Bentone...
2.7 Nozzle and pressure Due to different furnace geometries and capacities, it is not possible to recommend a nozzle model. Nozzle: 45° Solid/semi-solid 60° Solid/semi-solid Pump pressure 14 bar (12-16 bar) Bentone...
1060 93,70 1111 97,88 1161 101,85 1208 1039 26,00 96,81 1148 101,50 1204 1035 106,04 1258 1081 110,33 1308 1168 The table applies to oil with a viscosity of 4.4 mm /s (cSt) at a density of 830 kg/m Bentone...
Page 11
1267 1089 24,00 1254 1078 1297 1116 1341 1153 1382 1188 26,00 1359 1168 1406 1209 1453 1249 1497 1287 The table applies to oil with a viscosity of 4.4 mm /s (cSt) at a density of 830 kg/m Bentone...
3.1.3 Inspection and maintenance Refer to servicing schedule 3.1.4 Before commissioning A 3-stage thermostat must be installed before operation, contact Bentone for more information about the appropriate product. 3.1.5 Start up In order to obtain the correct setting, a flue gas analysis and temperature measurement must be carried out.
The vacuum should not fall below -0.3 bar in the suction line during start-up. 4.4.1 Proposed pipe routing for oil distribution systems without transport pump This type of connection should be used only when the oil has a viscosity less than 6 mm²/s. Oil fi lter Bentone...
• The connection should be made in accordance with the wiring diagram. • Fuse rating is as required. If any electrical connection is used other than that recommended by Bentone, there may be a danger of damage to property and personal injury.
4.7 Check oil line seals Once the burner has been installed and commissioned, the seals of the various coupling elements should be checked (A). If there is any leakage, retighten the connections. Use Loctite 5188 on threaded oil lines. 165 105 82 Bentone...
P3 air damper step 3 =72° P3 off, MV3 disconnection =60° This is an example of nozzle selection and air/insert setting. Selection of output and connection between the different power stages must be selected and adjusted so that the system achieves good functionality. Bentone...
Recommended excess air Oil type Excess air, fl ue gases Max. % % CO Lambda 1.2 Light oil, B10 heating oil/ 3–5 ≈12.5 15.4 biofuel mix (as per the defi nition in DIN V51603-6). RME according to (EN 142 14 FAME) Bentone...
Measure and note the lowest air pressure in the entire work area. Set the air pressure switch to about 10-15% lower than the lowest noted pressure. Test run the burner and check the function in the entire work area. Refi t protective cover. Bentone...
Close the boiler/hinged fl ange, refi t the Euro plugs and switch on the main power supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, fl ue gas analysis and soot test must be carried out following installation. 165 105 84-2 Bentone...
Slide in the burner and tighten the nuts (H). Refi t the Euro plugs and switch on the main power supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, fl ue gas analysis and soot test must be carried out following installation. Bentone...
Refi t the Euro plugs and switch on the main power supply. Start burner and check/adjust combustion. For B 70/B 80, which use SQM 33, the following parameters must be used to achieve the correct motor rotation direction. Parameters 601.00:0, 601.01:1, 602.00:0 and 602.01:1. Bentone...
Technical data for correct output). Start burner and check/adjust combustion. When servicing oil-bearing components, check for oil leakage when the burner is commissioned after servicing. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. Bentone...
Once the burner has been installed and commissioned, the seals of the threaded oil lines. various coupling elements should be checked (A). If there is any leakage, retighten the connections. When servicing/replacing components that affect combustion, fl ue gas analysis and soot test must be carried out following installation. Bentone...
• Check fan wheel for damage and dirt. Replace a damaged, soiled or unbalanced fan wheel. • Check motor shaft and bearings. If they are worn, replace the motor or bearings. Use the rear screw on the cover to attach the vibration sensor. Bentone...
Ignition system with flame guard 10 years 250,000 cycles UV flame sensor 10,000 h Damper motor 500,000 cycles Contactor 10 years 500,000 cycles The burner and its components must be recycled according to applicable regulations. 165 405 08 2021-12-07 Bentone...
Change the oil pump oil fi lter in accordance with the following. - Close the oil valves - Unscrew the cover on the pump. - Replace the oil fi lter. - Replace head gasket. - Mount the cover on the pump. - Open the oil valves. 165 305 27 Bentone...
Vacuum gauge port 5. Inlet Oil under pressure 1. Gear set By passed oil returned to tank, or to suction 2. By-pass hole 6. Pressure adj u stment 7. To nozzle 3. Pressure gauge port 4. By-pass plug installed 8. Return Bentone...
Manual reset with remote reset (optional) The remote reset shall be installed with a cable connected from X8-04.1 to X3-05.2 and reset button installed in preferred place. 165 105 55-2 Bentone...
S7 Main switch X53 Connection air damper with local regulations. S8 Air pressure switch X56 Connection display 8.4 Component electric box Switch 0-1 Fuse Automatic control unit LMV Contactor Thermal overload protection AZL display for LMV automatic control unit Disconnector Bentone...
Example: Modulating burner The system components (display and operating unit, actuators) are connected directly to the LMV37.4... basic unit. All safety-related digital inputs and outputs of the system are monitored by a contact feedback network. 165 405 09 Bentone...
6.3 AT (DIN EN 60127 2 / 5) Mains supply: Input current depending on the operating state of the unit Under voltage Safety shutdown from operating position at mains voltage LMV37.400A2 Approx. AC 186 V Restart on rise in mains voltage LMV37.400A2 Approx. AC 195 V Bentone...
Page 37
X5-02 Pin 2/3 RAST plug Function / Outputs Pin number X3-05 Pin 1 X4-02 Pin 2/3 X6-03 Pin 2/3 X8-02 Pin 1/3 X7-01 Pin 2/3 X7-02 Pin 2/3 X3-05 Pin 2 0° 0° 0° Legend to the sequence diagrams Bentone...
Page 38
Postpurge time (t3) Evacuation of test space Atmospheric pressure test Filling of test space Gas pressure test Gas shortage waiting time Valve proving is performed depending on the parameter settings: Simultaneously with the prepurge time and/or the afterburn time. Bentone...
Page 39
Only with fuel train Lo and 2 fuel valves Parameter 223: Repetition limit value gas pressure switch-min in connection with gas shortage program parameter 246 (phase 90) Max. drop-in/response time for air pressure switch Alternative to valve proving Alternative to pressure switch-max (Pmax) or POC Bentone...
Page 40
0°/10% Position as supplied (0°) 90°/100% Actuator fully open (90°) Input/output signal 1 (ON) Input/output signal 0 (OFF) Input permissible signal 1 (ON) or 0 (OFF) Bentone...
Protection earth (PE) Supply for fuel meter Shielding: Input fuel meter For shielding the cables on the VSD, refer to: • Siemens SED2 VSD Commissioning Manual (G5192), chapters 4 and 7, or • Danfoss Operation Manual VLT 6000 (MG60A703), chapter Installation Bentone...
Page 42
Speed feedback signal Speed feedback signal Signal reference PWM speed output PWM speed output Signal reference DC 24 V external DC 24V external Controller input 4...20 mA Controller input 4...20 mA Power source Power source Controller Analog Analog Controller Bentone...
• For changing to a higher menu level (press button for 3…8 s) • For changing the operating mode (press button for >8 s) /reset - Enter in parameter setting mode - Reset in the event of fault - One menu level down Bentone...
Page 44
Figure 4: Meaning of display Fault status message Flame present Valve controlled Ignition controlled Fan motor controlled Oil preheater on Heat request from controllers Parameter setting mode Info mode Service mode h min s Actuator closing Actuator opening Unit of current display Bentone...
Postpurge time (t3) (abortion when load controller ON) Ph80 Valve proving test evacuation time Ph81 Valve proving test time atmospheric pressure, atmospheric test Ph82 Valve proving filling test, filling Ph83 Valve proving time gas pressure, pressure test Ph90 Gas shortage waiting time Bentone...
Change to normal Change to normal display display >3 s <8 s Info level /reset >3 s <8 s /reset or automatic return after timeout of Service level menu operation (parameter 127) >8 s >1 s Parameter level Parameter level Bentone...
Page 47
Basic unit Air-fuel ratio control curves (primary setting) /reset Bild 388e/1109 /reset Air-fuel ratio control /reset The following sections Actuator explain the operating philosophy behind the parameter levels using a number of examples. /reset Error histery /reset Process data Bentone...
Page 48
Standardized speed Number of faults Error history: 701-725.01.Code 701. chronological error list index value of index Indexlista: 04 = error phase 01 = error code 05 = startup counter 02 = diagnostic code 06 = output 03 = error class Bentone...
Page 49
Press button combination to display CodE When releasing the buttons, 7 bars appear the first of whishes. h min s Press to select a number or letter. h min s Press to confirm the value /reset Bentone...
Page 50
OFF UPr. h min s 10.3.7 Safety loop A unit whose safety loop and / or burner flange contact is open, and a controller ON signal is present, displays OFF S. h min s Bentone...
400 for initial commissioning and for setting air-fuel controll. /reset 201: appears fl ashing. h min s Press to go to the settings for air-fuel ratio control and parameter /reset 201 for selecting the operating mode. Bentone...
Page 52
23 = HO mod with circulation • • 24 = HO 2-stage with circulation • 25 = HO mod without circulation control • • 26 = HO 2-stage without circulation control • 27 = HO 3-stage without circulation control • Bentone...
Page 53
Select your setting by pressing one of the buttons Press to save the setting for parameter 542: VSD This manual describes /reset “0=VSD OFF” type burners. Press: to return to parameter level. To the next parameter Back to the previous parameter Bentone...
10.5.1 10.4.1 Definition of curves Air-fuel ratio control is defined via the 2 or 3 static output points. To switch the valves on and off, switch-on and switch-off points must be defined. The following assignments apply: Bentone...
Page 55
The running speed of the actuators is fixed at 5 seconds for a positioning angle of 90° for SQM33.4, SQM33.5, and SQN1. The speed is 10 seconds for a positioning angle of 90° for SQM33.6. The SQM33.7 requires 17 seconds for a positioning angle of 90°. Bentone...
Page 56
In the operating position, the burner’s output can be adjusted between operating points P1 and P2 or P3 in accordance with the load controller’s presetting, as described in chapter Adjustment of output. Ignition position P0 is not approached anymore. It can only be reached via curve adjustment. Bentone...
Page 57
Identification of start for setting the curve parameters. Note! You are now given the choice of proceeding with the warm settings by pressing /reset (refer to chapter Warm settings for modulating mode «Lo2-steg"och "Lo3-steg", or settings off mode by pressing - Bentone...
Page 58
Ignition position P0 can be set only when symbol or is no longer highlighted. Keep depressed and, for VSD as well as Press - + to adjust the value. When symbol or is no longer highlighted, the next curvepoint P1 can be selected with Bentone...
Page 59
Ignition position P0 can be set only when symbol or is no longer highlighted. Keep depressed and, for VSD as well as Press to adjust the value. When symbol or is no longer highlighted, the next curvepoint P1 can be selected with Bentone...
Page 60
Keep depressed and, for VSD Press to adjust the value. When symbol or is no longer highlighted, the next curvepoint P2 can be selected with Bentone...
Page 61
OFF UPr is still active until all curvepoints are set. When symbol or is no longer highlighted, ESC can be pressed a second time. The warm settings for air-fuel ratio control of the LMV37.4... have now been configured. Bentone...
Page 62
Example: Curvepoint Low-flame position P1. Change to parameter 954 /reset >1 s Parameter 954: flashes. The intensity of flame in % is shown on the right. Example: 954: /reset Release /reset to return to curvepoint Low-fire position P1. Bentone...
Page 63
“0=no valve proving” or “1=valve proving on startup”. The automatic control unit should be set to “Index 0 = no-load position”. The automatic control unit should be set to “Index 0 = no-load position”. Bentone...
Page 64
1 = active (postpurge position) Factory settings marked with bald text. When the Purging in the lockout position function is used, the fan may only be powered via a contactor and must not be connected directly to LMV37.4 (X3-05 pin 1)! Bentone...
Page 65
23 hours and 45 min of uninterrupted operation, followed by an automatic restart. When forced intermittent operation is inactivated the burner will run continuously. Forced intermittent operation is a standard feature. 279 Oil: Forced intermittent operation 0 = inactivate 1 = activated Factory settings marked with bald text. Bentone...
To continue with the setting work, you need to log into service engineer level. See 5.3.4. After login is complete, continue with the setting work as shown below. Press for parameter level 000. Press /reset Display: Parameter 050, flashes, index 00, and value 0 do not. /reset Display: Parameter bAC_UP /reset Bentone...
Page 67
If an errror occurs during the backup process, a negativ value is displayed. For error diagnostics, the cause of the error can be determined from the diagnostic code of error message 137 (see Error code list) Press four times until the top menu is displayed. Bentone...
Page 68
After login is complete, continue with the setting work as shown below. Press for parameter level 000. Press /reset Display: Parameter 050, flashes, index 00, and value 0 do not. /reset Display: Parameter bAC_UP Press to select parameter rESstorE /reset Bentone...
Page 69
Press to select the restore process. /reset Press to shift the value in change mode 1 position to the left. Display: Value 1 flashes To detect potential dispalay errors, the value is displayed 1 place shifted to the left Bentone...
The display shows current error code c: alternating with diagnostic code d: (refer to Flash code list). Example: Error code 4/diagnostic code 3 h min s When pressing for 1...3 s, rESEt appears on the display. /reset Bentone...
Page 71
SEr and then OPErAtE. >5 s For a list of parameters, see table 5.3.3. /reset h min s When the button is released, a change to info / service mode is made. >8 s /reset h min s Bentone...
Page 72
The unit initiates safety shutdown. The display shows current error code c: alternating with diagnostic code d:. h min s Press 1...3 s, to return to the normal display. /reset Example: Error code 12 / diagnostic code 0 h min s Bentone...
Page 73
Display: Parameter 701. flashes, index 01: and example value 201 does not. h min s Press to go to index 01: /reset Display: Parameter 701. does not flash, index 01: flashes, value 201 does not. h min s To the next index Back to the previous index. Bentone...
Page 74
/reset Press to go to display mode. /reset Display: Value 56 (number of startup) h min s Press to return to the index. Display: Parameter 701. does not flash, index 05: flashes, characters ._._ h min s do not. Bentone...
Page 75
To the next index Back to the previous index. When this display appears, you have reached the end of the error history. Display – End – appears flashing. h min s Press twice. HISt 700: for error history h min s Bentone...
OFF UPr. h min s 10.8.3 Safety loop A unit whose safety loop and / or burner flange contact is open, and a controller ON signal is present, displays OFF S. h min s Bentone...
Select another burner type than the one already selected by pressing one of the buttons Confirm this selection with The automatic control unit is now reset. /reset h min s Restart the setting process for the LMV automatic control unit as specified in 3.2.1. Bentone...
LoAd 0.0 means Manually OFF. As long as the Manual OFF is active, OFF appears on the normal display flashing. To deactivate and to change to automatic operation, press for 3 seconds. Then OFF appears without flashing in the display. Bentone...
Page 79
Manually OFF must not be used just to put a burner out of operation when doing mounting work, or when the burner is not ready for operation. The safety notes contained in chapter Safety notes must be observed! Bentone...
Preheater temperature too low Check preheater function New oil type Adjust the preheater‘s set operating temperature Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. 165 105 09-2 2021-01-21 Bentone...
Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. Temperature of the oil from the tank is too low, increase the temperature of oil from tank Clean the pump filter 165 105 09-2 2021-01-21/2 Bentone...
Pump worn Replace the pump Pump run using impure oil that has worn the Replace pump and install self-cleaning pump out prematurely filter in the oil system Blocked pump filter Check, clean pump filter 165 105 09-2 2021-01-21/3 Bentone...
14. Log of flue gas analysis Owner Adresss Tel. no: Installation Tel. no: Boiler Type Make Power Bentone Burner Serial no. Type Model Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke number Flue gas temp. °C...
Page 108
EU Declaration of conformity Bentone Oil Burners Type BF 1 B 45 B 80 ST 146 B 55 B 30 B 65 B 40 B 70 This declaration of conformity is issued under the sole responsibility of the manufacturer. The object of the declaration described above is in conformity with:...
Need help?
Do you have a question about the B 70i-3R FAME J and is the answer not in the manual?