GE MDP Instruction Manual page 56

Digital time overcurrent relay
Hide thumbs Also See for MDP:
Table of Contents

Advertisement

7 MODBUS PROTOCOL
Table 7–1: MODBUS MEMORY MAP (Sheet 2 of 4)
REGISTER CONTENTS
1011
Phase A trip current
1013
Phase B trip current
1015
Phase C trip current
1017
Ground trip current
1019
Trip time
1021
Breaker Status
1022
Relay Hardware Status
COMMNET COMMUNICATION STATISTICS REGISTERS
1500
Device Status
1501
Total Communication errors
1502
CRC Errors
1503
Transmit Failures
1504
Receive Time-out
1505
Receive Errors
EVENT REGISTERS
2000
Event Code - EVENT 1
2001
Hour
7
2002
Minute
2003
Seconds
2004
Milliseconds
2005
Event specific data 1
2006
Event specific data 2
2007
Event specific data 3
2008
Event specific data 4
2009
Event specific data 5
2010
Event specific data 6
2011
Event code - EVENT 2
2012
Hour
2013
Minute
2014
Seconds
2015
Milliseconds
7-
4
Courtesy of NationalSwitchgear.com
RANGE
TYPE
R/W
0 to 10 A (5 A relay)
RO
0 to 2 A (1 A relay)
0 to 10 A (5 A relay)
RO
0 to 2 A (1 A relay)
0 to 10 A (5 A relay)
RO
0 to 2 A (1 A relay)
0 to 3 A (5 A relay)
RO
0 to 0.7 A (1 A relay)
0 to 999.99 sec.
RO
00 to 01h
RO
00 to 04h
RO
N/A
RO
N/A
RO
N/A
RO
N/A
RO
N/A
RO
N/A
RO
0 to 256
RO
0 to 23 hrs.
RO
0 to 59 min.
RO
0 to 59 sec.
RO
msecs
RO
0 to 256
RO
0 to 23 hrs.
RO
0 to 59 min.
RO
0 to 59 sec.
RO
msecs
RO
MDP Digital Time Overcurrent Relay
FORMAT CODE
Float
Float
Float
Float
Float
Unsigned Integer
00h: Closed, 01h: Open
Unsigned Integer
00h: Relay is OK
01h: Relay not responding to read
02h: Relay not responding to write
03h: Command error reported
04h: Fatal error in Relay
1 = ALIVE, 0 = DEAD
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
Unsigned Integer
GEK-100682D
BYTES
COMMNET
COMMAND
2
80/74/09-0Ah
2
80/74/0B-0Ch
2
80/74/0D-0Eh
2
80/74/0F-10h
2
80/74/11-14h
1
80/57/00h
1
80/57/03h
1
N/A
1
N/A
1
N/A
1
N/A
1
N/A
1
N/A
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
GE Power Management

Advertisement

Table of Contents
loading

Table of Contents