6.2 - Summary cooling and heating mode tables in Occupied mode
Water temperature
Temperature below 15°C* Temperature from15 to 35°C
Air °C Valve
Fan
ON
ON
ON
Water temperature
Temperature below 15°C*
Air °C
Valve
Heater
ON
ON
ON
ON
ON
ON
Water temperature - hot water circuit
Temperature below 35°C*
Air °C Heating valve
Cooling valve
ON
ON
ON
Legend
Heater
Electric heater
*
Cooling demand
The valve opens if the water temperature falls below 15°C. The valve
closes if the water temperature rises above 20°C.
**
Heating demand
The valve opens if the water temperature rises above 35°C. The valve
closes if the water temperature falls below 30°C.
Setpoint
Minimum fan speed
Medium fan speed
Maximum fan speed
Two-pipe changeover configuration
Valve
Fan
Two-pipe changeover plus two wires configuration
Temperature from15 to 35°C
Fan
Valve
Heater
ON
ON
ON
Four-pipe configuration
Fan
ON
ON
ON
Temperature above 35°C**
Valve
Fan
ON
ON
ON
Temperature from 35 to 43°C**
Fan
Valve
Heater
ON
ON
ON
ON
ON
ON
Temperature above 35°C
Heating valve
ON
ON
ON
Air temperature decrease
Air temperature increase
Note:
If the CRC temperature sensor is selected in the Heating Satsfied mode, the fan
operates to protect against cold draughts (see chapter "Cold draught protection").
Temperature above 43°C
Fan
Valve
Heater
ON
ON
ON
Cooling valve
ON
ON
ON
Fan
Fan
9