Siemens SIMATIC Compact FF Link Operating Instructions Manual page 84

Bus link
Table of Contents

Advertisement

Technical data
12.1 General technical data
Mechanical ambient conditions
The mechanical ambient conditions for the described components are specified in the table
below for sinusoidal vibrations.
Frequency range in Hz
10 ≤ f ≤ 58
58 ≤ f ≤ 150
Reduction of vibrations
If the described components are subject to big shocks or vibrations appropriate measures must
be taken to reduce the acceleration or the amplitude.
We recommend fixing the described components on damping materials (rubber-metal anti-
vibration mountings, for example).
Checking mechanical ambient conditions
The following table provides information on the type and scope of checks regarding mechanical
ambient conditions.
Checking for
Vibrations
Shock
Climatic ambient conditions
The described components can be used in the following climatic ambient conditions:
Ambient conditions
Temperature:
Horizontal installation
Vertical installation
Temperature:
any type of installation
84
Continuous
0.0375 mm amplitude
g constant acceleration
0.5
Test standard
Vibration test according to
IEC 60068 Part 2-6 (sinusoi‐
dal)
Shock test in accordance
with IEC 60068 Part 2-29
Permitted range
from -40 to 70 °C
from -40 to 50 °C
from -40 to 70 °C
Infrequently
0.075 mm amplitude
g constant acceleration
1
Remarks
Type of vibration:
Frequency sweeps with a sweep rate of 1 octave/mi‐
nute.
5 Hz ≤ f ≤ 8.4 Hz, constant amplitude 3.5 mm
8.4 Hz ≤ f ≤ 150 Hz, constant acceleration 1 g
Period of oscillation: 10 frequency sweeps per axis in
each of the 3 axis which are vertical to each other.
Type of shock: half-sine
Strength of shock:
15 g peak value, 11 ms duration
Shock direction:
3 shocks each in +/- direction in each of the 3 axes
that are vertical to each other
Remarks
● Compact FF Link
6ES7655-5BA00-0AB0
● BM Compact FF Link
6ES7655-5EF00-0AA0
Active field distributors
See Operating Instructions
tive Field Distributor, DP/PA Link and Y Link
Operating Instructions, 03/2015, A5E35651552-AA
DP/PA coupler, Ac‐
Compact FF Link

Advertisement

Table of Contents
loading

Table of Contents