8. Reversing valve control circuit
Reversingvalve
valve
DC voltmeter
or multimeter
Reversing valve control circuit will switch reversing valve ON/OFF according to instruction from indoor
microcomputer depending on the operation condition shows in Table 8-1.
Voltage at Q701 (between Collector and Emittor) in each operation condition is approximately as shown
in Table 8-1 when measured by multimeter.
Table 8-1
Cooling
Heating
Dehumidifying
Power P.W.B.
CN2
2
D701
4
Q701
R705
R706
V
D-0V
Operation condition
General operation of cooling
In normal heating operation
MAX. rotation speed instructed by indoor
microcomputer after defrost is completed
Defrosting
Sensor dry
C-35V
MAIN P.W.B.
12V
R701
PQ701
CN4B
CN4A
 
6
6
Fig. 8-1
Collector voltage of Q701
About 0.8V
About 35V
About 35V
About 0.8V
About 0.8V
- 64 -
Micro
computer
24