7.2.4 DRM (Australia AS4777)

Function
According to Australia AS 4777.2-2015, solar inverters need to support the
function of demand response mode (DRM), and DRM0 is a mandatory
requirement.
This function is disabled by default.
Figure 7-12 Wiring diagram for the DRM function
Table 7-3 DRM requirements
Mode
DRM0
Issue 02 (2022-03-10)
Description
The default underfrequency protection threshold is 47.5 Hz,
and the default protection time threshold is 0.1s.
NO TE
The demand response enabling device (DRED) is a power grid dispatch device.
Port on the inverter
DI1 and GND of the COM
port
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interaction
Requirements
● When switches S0 and S9 are
switched on, the solar inverter
should be turned off.
● When switch S0 is switched
off, and switch S9 is switched
on, the solar inverter should
be grid-tied.
65