Table 5-2 Cable description
No. Cable
1
2
3
4
Note a: The minimum cross-sectional area of the cable should be selected based
on the rated value of the AC fuse.
Issue 02 (2022-03-10)
Type
DC input
Common outdoor PV
power
cable in the industry
cable
(Optional)
Outdoor shielded
Signal
twisted pair cable
cable
AC output
● Not using the PE
power
equipotential point
at the AC output
a
cable
port: two-core (L
and N) outdoor
copper cable
● Using the PE
equipotential point
at the AC output
port: three-core (L,
N, and PE) outdoor
copper cable
PE cable
Single-core outdoor
copper cable and M6
OT terminal
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connection
Recommended
Specifications
● Conductor cross-
sectional area: 4–6
2
mm
● Cable outer
diameter: 5.5–9
mm
● Conductor cross-
sectional area:
– Combined
crimping of
cables on the
port: 0.20–0.35
2
mm
– Crimping the
cables on the
port without
combining
them: 0.20–1
2
mm
● Cable outer
diameter:
– 4-hole rubber
plug: 4–8 mm
– 2-hole rubber
plug: 8–11 mm
● Conductor cross-
sectional area: 4–6
2
mm
● Cable outer
diameter: 10–21
mm
2
4–10 mm
Source
Prepared
by the
customer
Prepared
by the
customer
Prepared
by the
customer
Prepared
by the
customer
32