5.6 MODBUS Setting

This page enables the user to set MODBUS configurations.
MODBUS TCP Configuration
Enable MODBUS TCP: This field allows user to enable or
disable the MODBUS TCP protocol. Available values are
"Disabled" and "Enabled", default value is "Disabled".
MODBUS Port: This field allows user to set the specific port
for the user that allows accessing the interSeptor Pro-XP via
Modbus protocol. Available values are from 1 to 65535,
default value is 502.
MODBUS RTU Configuration
Enable MODBUS RTU: This field allows user to enable or
disable the MODBUS RTU protocol. Available values are
"Disabled" and "Enabled", default value is "Disabled".
Slave Address: This field allows user to set the slave address
of MODBUS RTU. Available values are from 1 to 247, default
value is 1.
Baud Rate: This field allows user to set the communication
baud rate. Available values are "9600", "19200", "38400",
"57600" and "115200", default value is "9600".
6 Alert & Logs

6.1 Alert Table

This table display current alerts.
ID: This field defines the index of alert.
Time: This field defines the happened time of alert. The
format is dd/mm/yyyy hh:mm:ss .
Alert Description: This field defines the description of alert.
Please refer to Alert Message Definition.