Installation
Mounting the DynaView (2A55) human interface
Figure 5. Installing the DynaView and tilt bracket
1. If the tilt bracket is not required (DynaView mounted directly to door) skip Steps
2, 3, 6, and 8.
2. Attach the grommet in the 1" hole in the flat mounting panel (tilt bracket).
3. Mount the tilt bracket base to the door using the two screws provided.
4. Attach the Phoenix connector to the three foot long DynaView cable.
5. Attach the Phoenix connector on the DynaView cable to the DynaView (red-1,
black-2, green-3, and white-4).
6. Thread the other end of the DynaView cable through the hole in tilt bracket flat
mounting panel.
7 . Attach the DynaView to the flat panel using the four screws/nuts provided. Watch
that the cable does not become pinched between DynaView and the flat mount-
ing panel. Only tighten enough to slightly compress the gasket. Be careful to
NOT bottom out the DynaView against the panel, only the gasket should touch
the panel.
8. Attach the flat mounting panel to the tilt bracket brace using the two threaded
adjustment wheels provided.
9. Thread the DynaView cable through the hole in door.
10. Attach the DynaView cable to the four pin connection on LLID 2A50, power sup-
ply. (Note: this cable can be attached to any LLID as all LLIDs will be connected
together on IPC bus.)