Wiring Separation; Internal Structure - Siemens FC2005 Installation, Operation And Maintenance Manual

Fire alarm control panel
Table of Contents

Advertisement

Wiring Separation

All high voltage and non-power limited wiring must be kept separate from power limited wiring.
A separation of at least 1/4 inch must be maintained with high voltage and non-power limited
wiring running in separate conduit openings from power limited wiring.
Dialer
P2
NAC-1
NAC-2

Internal Structure

Battery bracket
left
7 Optional field wire knock-outs
Enclosure
Power supply
Battery bracket
right
Batteries
37
firealarmresources.com
Relay-1
Relay-2
Relay-3
Relay-4
AC input
Main board assembly