Advertisement

The schematic below shows the wiring for the Flue Damper.
COM
NO COM
Volt Free
Volt Free
Fault
Relay
6A
PWM
Out
In
OT
Gnd
LV
Open
PWM
External
Therm
Pump
Interlock
12A
12B
Turn on the power to the boiler and recommission the boiler to configure the connected motorised flue damper.
Note: If you are adding a Motorised Flue Damper to an Imax Xtra 2 that already has a Boiler Pump controlled directly from the
boiler you must observe the following:
The On/Off Controlled Boiler Pump MUST be converted to Modulation Controlled Boiler Pump.
If the Boiler pump has a PWM Modulation Input available you can use the schematic shown in Figure 3.
If the Boiler pump only has a 0-10V Modulation Input available you need to order the 0-10V Pump Kit. The schematic
showing the wiring is shown in the instructions which are provided with the kit.
IMAX XTRA 2 -
Flue Damper Kit Instructions
INSTRUCTIONS
NO
Out
In
N
L
230V
DHW Pump or
Burner
External
Hea�ng
Circuit 2 Pump
Relay
Interlock
6B
5
4A
Gnd
C
CL-
C
CL-
C
CL-
Room
Room
Room
Stat 1
Stat 2
Stat 3
QAA55
QAA55
QAA55
11
10A
10B
10C
Power from main supply
MUST be the same phase
as the boiler supply.
Boiler
Pump
Flue
Damper
M
External System
Controls
N
L
N
L
Out
In
Hea�ng
Boiler Pump
Switched
Circuit 1
or
Live 1
Pump
System Pump
4B
3
2A
0-10
Gnd
DHW
Outside
Header
0-10V
Sensor
Sensor
Sensor
Input
9A
9B
9C
9D
Fig. 2
PWM
Out
In
Gnd
LV
PWM
External
Pump
Interlock
12A
12B
Fig. 3
Fused Spur
N
Out In
L
Switched
Mains
Live 2
In
2B
1
5