When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Heating.
Page 2
Boilers that show CAT. I on the data badge cannot be converted. kW (NG) Product No. Imax Xtra 2 80 225464 Imax Xtra 2 120 225465 Imax Xtra 2 160...
KIT CONTENTS HEAT INPUT "Q" = 2797 GROSS 80kW IMAX XTRA 2 kW (Btu/h) kW (Btu/h) M A X . 80.0(272,950) 88.8(303,000) CE 682118 M I N . 24.0(81,900) 26.6(90,750) 230V 50HZ FUSED AT 13A HEAT OUTPUT "P" = POWER CONSUMPTION 110W I.P.20...
Page 4
CASING REMOVAL AND ACCESS CONTROL POD REMOVAL (SCREW) SECTION 3.7 SECTION 3.8 REMOVAL AND ACCESS FAN REMOVAL Top Panel 1. Remove the two bolts at the rear of the top panel. Lift up from side panel retention studs and remove. Control Pod 2.
Page 5
REMOVING THE ORIFICE PLATE 1. Whilst supporting the gas valve, remove the four bolts Replace the four bolts that have been removed with the securing the gas valve to the venturi. four new M5 x 12mm bolts supplied in the conversion kit. Ensure an even tightening sequence of the bolts.
Page 6
RE-LOADING THE NATURAL GAS PARAMETERS Steps to follow for boiler that has been previously configured as an LPG boiler 1. Refer to safety section. 3. Follow the steps below to upload the parameters for Natural Gas. 2. Enter service mode using access code 529. Please refer to the Installation &...
GAS VALVE ADJUSTMENT Maximum rate adjustment Minimum rate adjustment 1. Switch the boiler on and set the boiler into service mode 4. To ensure the boiler operates at minimum rate without maximum which will last for 10 mins but can be exited modulating, set the fan speed to minimum following the earlier.
Page 8
ACCESSING SERVICE MODE FOR GAS VALVE ADJUSTMENT TARGET ACTUAL TARGET ACTUAL 75° 75° 75° 75° Hot Water Heating No Demand Demand On MENU Switched Live Control 8° 100% Burner Stabilisation Press MENU Menu Status Settings Service Configuration Access Level Press Service To set the boiler to run at To set the boiler to run at Maximum Rate for 10 Minutes...
Page 9
PROPANE DATA LABEL AND OVERLAY 1. Ensure that the boiler has had the orifice plate removed and 4. Once all details have been recorded, adhere one of the two the parameters have been updated for Natural Gas. tear off strips over the existing label at the rear of the boiler and the other one over the existing label on the cover of the 2.
At Ideal Heating we take our environmental impact seriously, therefore when installing any Ideal Heating product please make sure to dispose of any previous appliance in an environmentally conscious manner. Households can contact their local authority to find out how.