Page 1
When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Ideal Heating.
Flue Damper Kit Parts ............2 Electrical Connections of the Motorised Flue Damper ..3 1.1 INTRODUCTION The following document provides instructions on how to install the Imax Xtra 2 motorised flue damper. 1.2 FLUE DAMPER KIT PARTS The kits consist of the following parts: 1.
Connect the Flue Damper Feedback wire to Pin P3 of the screw terminal of the flue damper PCB. Cable Grommet Cable Grommet Flue Damper PCB Approximate location of Earth point once PCB cover removed Screw Terminals IMAX XTRA 2 - Flue Damper Kit Instructions...
Page 4
PCB Cover Bottom Screw Using the figures below as a guide connect the wiring from the flue damper to the Imax Xtra 2 as follows: Remove connector I3_CN from Installation Connection I3. Connect the Live wire to Pin 3 of connector I3_CN.
Page 5
Turn on the power to the boiler and recommission the boiler to configure the connected motorised flue damper. Note: If you are adding a Motorised Flue Damper to an Imax Xtra 2 that already has a Boiler Pump controlled directly from the boiler you must observe the following: •...
Page 6
This is done at the Cascade Flue with Electronic Damper Control page shown by selecting the “Yes” option. The user can now proceed with the configuration of the boiler following the remainder of the commissioning process. IMAX XTRA 2 - Flue Damper Kit Instructions...
Page 8
& servicing of central heating systems At Ideal Heating we take our environmental impact seriously, therefore when installing any Ideal Heating product please make sure to dispose of any previous appliance in an environmentally conscious manner. Households can contact their local authority to find out how.