Service Walk Test Shows Extra Points
The Service Walk Test differs from the standard Walk Test in that POPITs whose switches
are set for a point number not programmed in the panel appear in the test.
Service Walk Test only available at Command Centers with panel wide scope: See
Command Center in the D9000/D7000 Series Control/Communicator Program Entry Guide
(74-07695-000) for a description of Command Center scope.
Warning, fire and other 24-hour points do not transmit reports during Service Walk
Test!
The steps below outline a simple Service Walk Test procedure. The flow chart on the next
page shows all the Service Walk Test options.
1. Choose a Command Center with panel wide scope to conduct the test. Be certain the
2. Enter a valid service passcode and press the ENT key to enter the Function List.
3. The display shows ### PTS TO TEST . Test the first detection device.
4. As you fault the detection devices, the Command Center emits a brief tone and
5. During the Service Walk Test you may want to see the points that remain untested.
6. After testing the last point, 0 PTS TO TEST displays. Press CLEAR. The display
Automatic time-out returns the system to idle text: If there is no point or Command
Center activity for 20 minutes, the walk test ends automatically. The Command Center
returns to idle text.
D9000/D7000 Series Installation and Troubleshooting Quick Reference
33317D 4/97
Basic Troubleshooting
display shows the idle disarmed text.
Press NEXT repeatedly until you reach the SERVICE WALK ? prompt. Press ENT.
displays the point text of the point tested for 60 seconds. After 60 seconds, the display
returns to the points to test message.
Extra Points display default text: If you incorrectly set the switches on a POPIT to a
point number that is not in your program for the panel, the default text for that point
number ( PT ### ) displays when you fault the point. The Program Record Sheet shows
the default text for all points.
Faulting the point a second time produces the tone and displays the point text, but
does not reduce the PTS TO TEST count.
When point text is displayed, press CLEAR. The display shows ## PTS TO TEST .
Press the CLEAR key. VIEW UNTESTED ? is displayed. Press ENT. ## PTS
UNTESTED is displayed. Press NEXT to see a list of the points that have not yet been
tested. Move through this list by pressing the NEXT key. To resume the Service Walk
Test, press CLEAR. ## PTS UNTESTED is displayed. Press CLEAR. ## PTS TO
TEST is displayed. Resume testing points. To end the Service Walk Test, press
CLEAR twice.
momentarily shows ALL PTS TESTED before returning to idle text.
Page 2