Quick Start Guide
2.5
Use check filters to validate configuration
Procedure
1. Position the Warning Level check filter on the detector as shown.
The check filters are provided in the commissioning kit.
Figure 2-5: Detector with Check Filter Installed
2. Check that the detector reading is within the range specified in the
factory acceptance test (FAT) certificate.
3. Repeat
4. Remove all filters and wait 30 to 60 seconds. Then verify that the
detector returns to Normal status (light-emitting diode [LED] is
green and blinking, and the output is 4 mA).
28
Step 1
and
Step 2
with the Alarm filter.
April 2021
Emerson.com/Rosemount