Emerson Rosemount 935 Quick Start Manual page 11

Open path combustible gas detector
Hide thumbs Also See for Rosemount 935:

Advertisement

April 2021
1.5
Install conduits and cables
The conduit and cable installation must comply with the following
guidelines:
To avoid water condensation in the detector, install it with the conduits/
cable entries facing downwards.
Use flexible conduits/cables for the last portion connecting to the
detector.
When pulling the cables through the conduits, ensure that they are not
tangled or stressed. Extend the cables about 12-in. (30 cm) beyond the
detector location to accommodate wiring after installation.
After pulling the conductor cables through the conduits, perform a
continuity test.
Quick Start Guide
Quick Start Guide
11