5. PI/O Module
Analog Input Module SAI01
SAI01 module specifications
Model name
Number of input points
Input insulation unit
Input signal level
Maximum applied voltage
Input impedance
Data update period
A/D conversion data
CMRR
Standard input accuracy
Cold junction compensation accuracy
Temperature drift
Power supply voltage drift
Input wire break characteristics
Input wire break detection time
Address setting
Diagnosis of trouble
Insulation resistance
Ability of insulation to withstand
voltage
Current consumption
Internal heat generation
Compatible terminal block units
Compatible options
Compativle I/O base unit
External dimensions
Weight
(Note1) Thermocouple type and temperature range can be set with the Engineering Tool. See
Chapter2,"Registering Hardware" in the "Engineering Tool Manual (6F8C1006)
98
Item
SAI01
8 points
8 points isolated together (input(-) side common)
Bipolar:  10 mVdc,  20 mVdc,  50 mVdc,  100 mVdc,  1 Vdc,  5 Vdc
Unipolar: 1-5 Vdc
J type: 0 to +200℃,0 to +400℃,0 to +400℃,0 to +600℃,+300 to +600℃
K type: 0 to +300℃,0 to +600℃,0 to +1200℃, +600℃ to +1200℃
T type: 0 to +300℃
E type: 0 to +200℃,0 to +400℃,0℃ to +600℃,0℃ to +800℃
R type: 0 to +1000℃,0 to +1600℃,+800℃ to +1600℃
S type: 0 to +1000℃,0 to +1600℃,+800℃ to +1600℃
B type: +600 to +1700℃
Each point set independently, mix of bipolar and unipolar not allowed.
In addition,DC1-5V and TC cannot be set together.(Note 1)
 30 V peak
1 M  or more
Bipolar: 355/302 ms(50/60 Hz filter, either can be selected)
Unipolar: 40 ms
Bipolar: -32000 to +32000 counts
Unipolar: +6400 to +32000 counts
100 dB or more (100 Vac-50/60 Hz)
mVN:  0.1% of full scale
±1℃
Within  0.015%/  C
Within  0.1% of full scale (in a system power supply fluctuation of  10%)
Down scale (TC input is Downscale/Upscale, set by Software)
2 seconds (bipolar), 10 seconds (unipolar)
Set from 1 to E (decimal 1 to 14) by front panel address setting switch.
Analog standard voltage, transmission, CPU, memory
100 M  or more (measured with 500 Vdc megger, between total inputs
and internal circuits)
500 Vac for 1 minute (between total inputs and internal circuits)
24 Vdc-50 mA or less (system power supply)
1.2 W or less (rated condition)
UTBA1, UTBA3 (when SDA01 module is used),EC352AI0151,
EC352AI0171
FIVC11, FIVC12, SDA01 (when UTBA3 is used)
UABU1
40 W x 90 H x 95 D mm (excluding protrusions)
200 g or less
Specification
TC:±0.2% of full scale
".