Modulex EXT Series Piping

MANDATORY REQUIREMENTS

SECTION 1: MANDATORY REQUIREMENTS
The following actions are mandatory to ensure proper piping and drainage of the Modulex EXT system.
CAUTION!
Local codes and authorities must be consulted prior to installation.
AERCO requires that the boiler loop to be de-coupled from the system loop. This can be achieved by
one of the following:
o Employing primary-secondary piping.
o Installing a hydraulic separator between the boiler and the system loop.
o Installing a heat exchanger
water treatment used in the system is not Aluminum compatible, the use of a heat exchanger
between the system and the boiler piping is MANDATORY.
AERCO requires cleaning of the whole system and to fit a mandatory Y-strainer on the return pipe to
the boiler, equipped with isolation valves (See Figure 13 through 20 at the end of this document).
For boiler replacement installations, cleaning of the whole system is required before connecting the
Modulex boiler (See Section 2.3 for Flushing, Treatment, and Cleansing tips and guidelines). Failure to
clean a system will limit it from the full benefits offered by the high efficiency Modulex boiler.
Boiler drain valve and condensate drain trap should be arranged to permit the fluids to drain freely, by
gravity, to a convenient floor drain.
For units installed in environments likely to experience freezing temperatures, it is necessary to ensure
that the condensate line and exhaust manifold are equipped with suitable freeze protection, such as a
heat trace line.
Relief valve must be installed vertically in the top, side, or to a valveless header connected to the water
supply outlet.
Locate water supply and return fittings (i.e. unions, elbows, etc.) a minimum of 6 inches from the boiler
fittings to prevent interference with the removal of the boiler panels and covers.
All piping and electrical connections (i.e. service switches, conduit boxes, etc.) should be located at a
minimum of 6 inches from the boiler panels and covers.
For all outdoor applications, electrical connections must either be NEMA4 rated or protected by a
suitable outdoor enclosure.
See Table 1 (Section 3) for sizing guidelines for the mandatory primary pump and boiler strainer.
A discharge pipe must be used and must not have an internal cross-sectional area less than the outlet
of the relief valve.
The discharge pipe must be installed so that there will be no danger of scalding to the boiler attendants.
See Figure 1, below, for a discharge pipe example on the Modulex boiler.
The relief valve point of discharge piping must have provisions for proper drainage.
TAG-0099
Application Guide
(e.g.
plate heat exchanger) between the boiler and the system loop. If
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913
Phone: 800-526-0288
Page 3 of 37