HIdRos SHA Series Technical Manual

HIdRos SHA Series Technical Manual

Swimming pool dehumidifiers
Table of Contents

Advertisement

Incorporated in this document are the following:
• Declaration of conformity
• Technical manual
• Dimensional drawing
Multiple instructions:
MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021
SWIMMING POOL DEHUMIDIFIERS
SHA
SERIES
TECHNICAL MANUAL
Read and understand
the instructions before
undertaking any work on
the unit
Original instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SHA Series and is the answer not in the manual?

Questions and answers

Summary of Contents for HIdRos SHA Series

  • Page 1 Incorporated in this document are the following: • Declaration of conformity • Technical manual • Dimensional drawing Read and understand Multiple instructions: the instructions before undertaking any work on the unit MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021 Original instructions...
  • Page 2 Reproduction, data storage and transmission, even partial, of this publication, in any form, without the prior written authorisation of HIDROS S.p.A., is prohibited. HIDROS S.p.A. can be contacted for all inquiries regarding the use of its products. pment and instructions regarding use and maintenance at any time, without notice.
  • Page 3: Table Of Contents

    5. UNIT START UP ...................................... 5.1 Preliminary checks ................................5.2 Description of the control panel ............................5.3 Remote control panel ................................. 6. USE ......................................... 6.1 Switch the unit on ................................6.2 Stop ....................................MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 4 8. DECOMMISSIONING ..................................... 8.1 Disconnect the unit ................................8.2 Disposal, recovery and recycling ............................8.3 RAEE Directive (only UE) ..............................9. DIAGNOSIS AND TROUBLESHOOTING ..............................................................10. DIMENSIONAL DRAWINGS ................................. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 5: Introduction

    In these instructions symbols have been used (described in the following paragraphs) to draw the attention of operators and users to the operations that have a higher risk and which must be performed safely. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 6: Potential Risks

    (special anchors or seismic vibrations to prevent disasters or earthquake. breakages or accidental falls ). MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 7: General Description Of Symbols Used

    ACTION REQUIRED A white symbol inserted in a blue circle indicates an action that must be done to avoid a risk. Safety symbols combined in accordance with ISO 3864-2: MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 8: Safety Symbols Used

    Any other use is prohibited because it may pose a potential risk to the health of operators and users. The unit is not suitable for operations in environments: • excessively dusty or potentially explosive atmospheres; • where there are vibrations; • where there are aggressive atmospheres MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 9 Contiene gas fluorurati ad effetto serra disciplinati dal protocollo di Kyoto Contains fluorinated greenhouse gasses covered by the Kyoto protocol The product label should never be removed from the unit. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 10: Safety

    If the loss is substantial ensure that measures are taken to adequately ventilate the area. Contain spilled material with sand, earth or other suitable absorbent material. Do not allow the refrigerant to enter drains, sewers or basements, as pockets of vapor can form. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 11: Prevent Inhalation Of High Vapor Concentration

    2.6.5 Further medical treatment Treat symptoms and carry out support therapy as indicated. Do not administer adrenaline or similar sympathomimetic drugs following exposure, due to the risk of cardiac arrhythmia. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 12: Technical Characteristics

    All units are supplied with the following control and protection devices: antifreeze protection sensor, high pressure switch with manual reset, low pressure switch with automatic reset, high pressure safety valve, compressor thermal overload protection, fans thermal overload protection. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 13: Accessories

    ISO1940. The electric motor has a separate electronic commuter (driver) and a speed modulation 0-10V, integrated PFC, burn out thermal protection (in case of considerable reduction of the power supply), protection degree IP54, serial interface card with modbus protocol RTU. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 14: Technical Data

    (4)Sound power level calculated according to ISO 9614, fan with available static pressure 50 Pa. The refrigerant data may change without notice. It is therefore necessary to refer always to the silver label placed on the unit. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 15 3.3.3 Pressure drops of hot water coil The graphic below shows the pressure drops of the hydraulic circuit that includes the hot water coil and the 3 way modulating valve. 75-100 150/153-200/203 1000 1250 1500 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 16 The desuperheater capacity in different conditions can be obtained multiplying the nominal capacity (See above), by the correction factor indicated in the table. 3.3.6 Pressure drops of desuperheater The graphic below shows the pressure drops of the hydraulic circuit that includes the desuperheater. 75-100 150/153-200/203 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 17 (Pa) Max. Nom. Min. 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 SHA 200/203 (Pa) Max. Nom. Min. 1300 1400 1500 1600 1700 1800 1900 2000 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 18: Operation Limits

    / or technical room w/o heat (attics, rooms communicating with the outside) as it may form condensation on the walls and inside the unit cabinet causing damages. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 19: Sound Data

    (according to set parameters), switches the compressor off, while the fan remains in operation. At the end of the defrost cycle, it is waited for the dripping time to allow the complete cleaning of the coil. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 20: Installation

    4.3 Personal protective equipment When operating and maintaining the unit, use the following personal protective equipment listed below as required by law. Protective footwear. Eye protection. Protective gloves. Respiratory protection. Hearing protection. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 21: Inspection

    It is important to keep the unit horizontal at all time to avoid damage to the internal components. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 22: Location And Minimum Technical Clearances

    In the main european markets, the minimum distance of electric appliances from water sources (basins, showers, pools, whirlpools) is 2 meters! Before the installation of the unit it is compulsory to check the national or local norms. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 23: Condensate Draining Connections

    The inlet minimum water temperature allowed is 55°C. This option is available only in combination with the electronic probe RGDD. It is not available in combination with remote mechanical hygrostat. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 24: How To Vent The Unit

    For a correct operation of the system it is mandatory to remove the air from the hydraulic circuit. To do that it’s recommended to use the proper vent valve positioned in front of the unit (see picture). 4.13 Desuperheater connection (RP01) MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 25: Installation Of Built-In Room Electronic Sensor (Rgdd)

    Any reversal of polarity will result in the non-functioning unit. The supervision connectivity cable must be telephone one type 2x0, 25 mm contacting the assistance. TELEPHONE LINE SERIAL INTERFACE CONNECTION CABLE WITH CARD ADAPTER UNITS MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 26: Connecting The Unit To Air Duct Channels

    In order to limit the noise, it is necessary that the air speed inside ducts would never exceed 4 m / sec. With crossing in order to reduce the transmission of vibrations MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 27: Grille Kit And Case For Ducted Version (Kgbh)

    It should be noted that the values in the numbered scale identify the desired The humidistat is supplied separately. For connection please refer to the wiring diagram supplied along with the unit. 115 mm MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 28: Electric Connections: Preliminary Safety Information

    If opened, the main switch cuts the power off to any electric heater and antifreeze device supplied with the unit, in- cluding the compressor crankcase heaters. The main switch should only be disconnected for cleaning, maintenance or unit reparation. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 29: Electrical Data

    For powering the unit remove the front panel; use the appropriate fairlead present in the side panel and connect the power cord to the terminal block in the cabinet. After connecting all cable carefully close the front panel. Power supply Electric connections MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 30: Electric Connections

    The ventilation openings must not be blocked. DESUPERHEATER PUMP Is used to operate the pump of the desuperheater unit. Dry contact, 230 V, maximum current consumption 1A. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 31: Unit Start Up

    • Before start up check that all panels are replaced in the proper position and locked with fastening screws. Do not modify internal wiring of the unit as this will immediately invalidate the warranty. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 32: Description Of The Control Panel

    In programming mode allows to scroll through the parameter codes or increases the values If press ed down for 5 seconds, it makes it possible to switch the unit on or off. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 33 Humidity set, in the bottom line will appear the label SETI. Temperature set, in the bottom line will appear the label SETH. makes it possible to modify the set points; MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 34 If there is damage to the remote control or there is a faulty connection, failure of communication will be indicated in the display with the message “noL” (no link). MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 35: Use

    Icon ON: the unit is on. Counter between two defrost cycles. Icon ON: the display shows the room temperature or hu- Not used. miditiy. Icon blinking: high pressure alarm is active. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 36 Unit equipped with electronic sensor Unit equipped with mechanical thermostat/hygrostat Unit in drip time after defrost Unit in drip time after defrost Unit equipped with electronic sensor Unit equipped with mechanical thermostat/hygrostat MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 37: Stop

    The units are supplied with a very sophisticated control system with many other parameters that are not adjustable by the end user; these parameters are protected by a manufacturer password. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 38: Alarm Reset

    Durch unterhalb der Beckenwassertemperatur liegende Raumtemperaturen können schwerwiegende Bauwer- kschäden hervorgerufen werden! Die GmbH haftet nicht für Schäden, die durch falsche Einstellungen der Sollwerte für Temperatur und Feuchte sowie durch unzureichende Beheizung der Schwimmhalle hervorgerufen wurden! MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 39: Maintenance Of The Unit

    In any case, the taps must remain closed as less as possible. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 40: Drive Access

    The top case and dischar- ge line of compressor are usually at high temperature. Care must be taken when working in their surroundings. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 41 Check for freon leaks In order to carry out operations on the refrigerant, it is necessary to observe the European Regulation 517_2014, tionary refrigeration, air conditioning and heat pump equipment”. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 42 • When replacing the compressor following a burn out, it is advisable to wash the cooling system with appropriate products including a • When under vacuum do not switch on the compressor. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 43: Decommissioning

    2011/65/EU (RoHS), but if abandoned in the environment it has a negative impact on the ecosystem. that for which it was designed, as there is a risk of electric shock if used improperly. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 44: Diagnosis And Troubleshooting

    Athi Hight room temperature. Replace faulty sensor Contact the Company Electrical heater thermal alarm cessary replace them. In (if present) ducted versions, check the pressure drop of the ducts. MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 45: Dimensional Drawings

    10. DIMENSIONAL DRAWINGS SHA 50 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 46 SHA 75 - 100 1054 1024 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 47 SHA 150/153 - 200/203 1234 1160 1204 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 48 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 49 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 50 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 51 MTEC.5800.GB-H-1 Operation and maintenance manual SHA series English Rev. H 02-2021...
  • Page 52 HIDROS Srl Technical data shown in this booklet are not binding. The reference languages for the whole documentation are Italian and English. The other languages are to be considered only as guidelines.