HIdRos HMA/Z Series Technical Manual

HIdRos HMA/Z Series Technical Manual

Industrial dehumidifiers with temperature control
Table of Contents

Advertisement

Quick Links

INDUSTRIAL DEHUMIDIFIERS WITH TEMPERATURE CONTROL
Incorporated in this document are the following:
• Declaration of conformity
• Technical manual
• Dimensional drawing
Multiple instructions:
MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021
HMA/Z
SERIES
TECHNICAL MANUAL
Read and understand
the instructions before
undertaking any work on
the unit
Original instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HMA/Z Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for HIdRos HMA/Z Series

  • Page 1 Incorporated in this document are the following: • Declaration of conformity • Technical manual • Dimensional drawing Read and understand Multiple instructions: the instructions before undertaking any work on the unit MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021 Original instructions...
  • Page 2 We declare under our own responsibility that the below equipment complies in all parts with the CEE and EN directives. The declaration of conformity is enclosed to the technical booklet enclosed with the unit. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 3: Table Of Contents

    5.1 Preliminary checks ................................5.2 Description of the control panel ............................5.3 Remote control panel ................................. 6. USE ......................................... 6.1 Switch the unit on ................................6.2 Stop ....................................6.3 Stand-by .................................... MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 4 8. DECOMMISSIONING ..................................... 8.1 Disconnect the unit ................................8.2 Disposal, recovery and recycling ............................8.3 RAEE Directive (only UE) ..............................9. DIAGNOSIS AND TROUBLESHOOTING ..............................................................10.DIMENSIONAL DRAWINGS .................................. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 5: Introduction

    In these instructions symbols have been used (described in the following paragraphs) to draw the attention of operators and users to the operations that have a higher risk and which must be performed safely. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 6: Potential Risks

    (special anchors or seismic vibrations to prevent disasters or earthquake. breakages or accidental falls ). MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 7: General Description Of Symbols Used

    ACTION REQUIRED A white symbol inserted in a blue circle indicates an action that must be done to avoid a risk. Safety symbols combined in accordance with ISO 3864-2: MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 8: Safety Symbols Used

    Any other use is prohibited because it may pose a potential risk to the health of operators and users. The unit is not suitable for operations in environments: • excessively dusty or potentially explosive atmospheres; • where there are vibrations; • where there are aggressive atmospheres MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 9 Contiene gas fluorurati ad effetto serra disciplinati dal protocollo di Kyoto Contains fluorinated greenhouse gasses covered by the Kyoto protocol The product label should never be removed from the unit. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 10: Safety

    2014. Contain spilled material with sand, earth or other suitable absorbent material. Do not allow the refrigerant to enter drains, sewers or basements, as pockets of vapor can form. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 11: Prevent Inhalation Of High Vapor Concentration

    2.6.5 Further medical treatment Treat symptoms and carry out support therapy as indicated. Do not administer adrenaline or similar sympathomimetic drugs following exposure, due to the risk of cardiac arrhythmia. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 12: Technical Characteristics

    (as a protection fans and compressors), control circuit automatic breakers, compressor contactors, fan contactors. The terminal board is supplied with voltage free contacts for remote ON-OFF and general alarm. 3.1.9 External remote condenser MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 13: Accessories

    It’s used to ensure the best resistance against the atmospheric agents and the operation in aggressive enviroments. The frame is made of stainless steel AISI 304, self-supporting with removable panels to facilitate inspection and maintenance of internal components. All screws and rivets are in stainless steel. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 14: Technical Data

    I dati relativi alla carica del refrigerante possono cambiare senza preavviso; è perciò necessario fare SEMPRE The refrigerant data may change without notice. It is therefore necessary to refer always to the silver label placed riferimento all’etichetta argentata posta sull’unità. on the unit. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 15 3,30 3,80 Input current 1,50 2,80 2,80 3,60 5,50 6,70 Input power 0,68 0,73 0,73 1,18 3,10 3,60 B (Low speed) Input current 1,40 1,50 1,50 2,20 5,20 6,40 MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 16 2,06 2,04 3,44 3,14 5,07 0,44 1,90 0,62 2,70 0,62 2,70 0,92 1,69 1,70 3,01 2,75 4,57 0,73 3,10 1,14 4,90 1,14 4,90 1,49 2,60 2,42 4,10 3,60 5,70 MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 17 It is recommended to move a single micro switch for each operating speed . The displacement of two or more micro switches may generate incorrect power supply voltages with malfunction or damage to the unit . MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 18: Operation Limits

    The units are designed to work in clean ambients and with the standard characteristics of the ambient air. It’s suitable not to install the unit in swimming pools or ambient with polluted and/or aggressive air. Contact the Company in case of necessity. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 19: Sound Data

    (according to set parameters), switches the compressor off, while the fan remains in operation. At the end of the defrost cycle, there is a timer delay to allow condensate water to clear from the coil. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 20: Installation

    4.3 Personal protective equipment When operating and maintaining the unit, use the following personal protective equipment listed below as required by law. Protective footwear. Eye protection. Protective gloves. Respiratory protection. Hearing protection. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 21: Inspection

    It is important to keep the unit horizontal at all time to avoid damages to the internal components. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 22: Location And Minimum Technical Clearances

    H1 = 20 mm = pressure difference inside the unit in mm water column Discharge pipe 10 Pa 1 mm water column the fan, in any case never less than 35 mm. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 23 HMA/Z with temperature control 4.9.1 How to remove the drip tray MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 24: Refrigerant Connections For Z Version

    - Pipelines diameter can be read in the Table depending on the unit size and on the lenght of refrigerant pipelines. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 25: Refrigerant Diameters Lines For Version Z

    The quantity of oil here metioned in the table, should be added for any syphon and meter of liquid line. Liquid line diameter (mm) The syphon must respect the following dimensions Ø MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 26: Refrigerant Schema

    Solenoid valve for external condenser Liquid receiver Solenoid valve for internal condenser Compressor Internal condenser drain solenoid Axial fan External condenser drain solenoid The cooling circuit principle diagram is purely indicative. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 27: Installation Of Built-In Room Electronic Sensor (Rgdd)

    Any reversal of polarity will result in the non-functioning unit. The supervision connectivity cable must be telephone one type 2x0, 25 mm contacting the assistance. TELEPHONE CABLE SERIAL INTERFACE CONNECTION CABLE WITH CARD ADAPTER UNITS MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 28: Connecting The Unit To Air Duct Channels

    ASLE ASRI ASVE Left hand side Supply Right hand side Supply Vertical Supply (standard) Flexible connection Self-tapping screws ø 3,9 mm or 4,2 mm MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 29: Fan Positioning

    In all units the supply fan can be oriented in 3 different directions. The operation has to be carried out exclusively in the factory. Standard ASRI ASVE ASLE Vertical Supply (standard) Left hand side Supply Right hand side Supply MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 30: Electric Connections: Preliminary Safety Information

    If opened, the main switch cuts the power off to any electric heater and antifreeze device supplied with the unit, in- cluding the compressor crankcase heaters. The main switch should only be disconnected for cleaning, maintenance or unit reparation. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 31: Electrical Data

    For powering the unit remove the front panel; use the appropriate cable gland present in the side panel and connect the power cord to the terminal block in the cabinet. After connecting all cable carefully close the front panel. Power supply Electric connections MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 32: Electric Connections

    The fans are directly connected to the fan; they are all at 2 speeds, with integrated thermal Max. speed protection. Min. speed REMOTE CONDENSER CONNECTION Under voltage contact 230V MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 33: Unit Start Up

    • Before start up check that all panels are replaced in the proper position and locked with fastening screws. Do not modify internal wiring of the unit as this will immediately invalidate the warranty. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 34: Description Of The Control Panel

    In programming mode allows to scroll through the parameter codes or increases the values If press ed down for 5 seconds, it makes it possible to switch the unit on or off. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 35: Remote Control Panel

    Humidity set, in the bottom line will appear the label SETU. Temperature set, in the bottom line will appear the label SETC. makes it possible to modify the set points; MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 36 If there is damage to the remote control or there is a faulty connection, failure of communication will be indicated in the display with the message “noL” (no link). MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 37: Use

    Icon ON: the unit is on. Counter between two defrost cycles. Icon ON: the display shows the room temperature or hu- Not used. miditiy. Icon blinking: high pressure alarm is active. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 38 Unit equipped with electronic sensor Unit equipped with mechanical thermostat/hygrostat Unit in drip time after defrost Unit in drip time after defrost Unit equipped with electronic sensor Unit equipped with mechanical thermostat/hygrostat MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 39: Stop

    The units are supplied with a very sophisticated control system with many other parameters that are not adjustable by the end user; these parameters are protected by a manufacturer password. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 40: Acoustic Signal Silencing

    RST label appears on the upper part of the display. In this case press the key to reset. The nO label appears on the upper part of the display. In this case the alarm is permanent; contact the Company. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 41: Maintenance Of The Unit

    In any case, the taps must remain closed as less as possible. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 42: Drive Access

    The top case and dischar- ge line of compressor are usually at high temperature. Care must be taken when working in their surroundings. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 43 Check for freon leaks In order to carry out operations on the refrigerant, it is necessary to observe the European Regulation 517_2014, tionary refrigeration, air conditioning and heat pump equipment”. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 44: Refrigerant Circuit Repair

    • When replacing the compressor following a burn out, it is advisable to wash the cooling system with appropriate products including a • When under vacuum do not switch on the compressor. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 45: Decommissioning

    2011/65/EU (RoHS), but if abandoned in the environment it has a negative impact on the ecosystem. that for which it was designed, as there is a risk of electric shock if used improperly. MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 46: Diagnosis And Troubleshooting

    Contact the Company Electrical heater thermal alarm cessary replace them. In (if present) ducted versions, check the pressure drop of the ducts. Atc1 Compressor alarm Compressor malfunctioning Contact the Company MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 47: Dimensional Drawings

    HMA/Z with temperature control HMA/Z 270 - 350 - 450 MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 48 HMA/Z HMA/Z 550 - 750 - 950 MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 49 HMA/Z with temperature control HMA/Z 270 - 350 - 450 (FARC) MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 50 HMA/Z HMA/Z 550 - 750 - 950 (FARC) MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 51 HMA/Z with temperature control HMA/Z 270 - 350 - 450 (Outdoor Unit) MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 52 HMA/Z HMA/Z 550 - 750 (Outdoor Unit) MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 53 HMA/Z with temperature control HMA/Z 950 (Outdoor Unit) MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 54 HMA/Z MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 55 HMA/Z with temperature control MTEC.6710.GB-D-1 Operation and maintenance manual HMA/Z series English Rev. D 02-2021...
  • Page 56 HIDROS Srl Technical data shown in this booklet are not binding. The reference languages for the whole documentation are Italian and English. The other languages are to be considered only as guidelines.

This manual is also suitable for:

Hma/z 270Hma/z 350Hma/z 450Hma/z 550Hma/z 750Hma/z 950

Table of Contents