Dehumidifiers for radiant cooling systems with heat recovery (48 pages)
Summary of Contents for HIdRos HDA Series
Page 1
Incorporated in this document are the following: • Declaration of conformity • Technical manual • Dimensional drawing Read and understand Multiple instructions: the instructions before undertaking any work on the unit MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021 Original instructions...
Page 2
Reproduction, data storage and transmission, even partial, of this publication, in any form, without the prior written authorisation of HIDROS S.p.A., is prohibited. HIDROS S.p.A. can be contacted for all inquiries regarding the use of its products. pment and instructions regarding use and maintenance at any time, without notice.
5.2 Description of the control panel ............................5.3 Remote control panel ................................. 6. USE ......................................... 6.1 Switch the unit on ................................6.2 Stop ....................................6.3 Stand-by .................................... 6.4 How to change the set points ............................MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 4
8. DECOMMISSIONING ..................................... 8.1 Disconnect the unit ................................8.2 Disposal, recovery and recycling ............................8.3 RAEE Directive (only UE) ..............................9. DIAGNOSIS AND TROUBLESHOOTING ..............................................................10.DIMENSIONAL DRAWINGS .................................. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
In these instructions symbols have been used (described in the following paragraphs) to draw the attention of operators and users to the operations that have a higher risk and which must be performed safely. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
(special anchors or seismic vibrations to prevent disasters or earthquake. breakages or accidental falls ). MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
ACTION REQUIRED A white symbol inserted in a blue circle indicates an action that must be done to avoid a risk. Safety symbols combined in accordance with ISO 3864-2: MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Any other use is prohibited because it may pose a potential risk to the health of operators and users. The unit is not suitable for operations in environments: • excessively dusty or potentially explosive atmospheres; • where there are vibrations; • where there are aggressive atmospheres MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 9
Contiene gas fluorurati ad effetto serra disciplinati dal protocollo di Kyoto Contains fluorinated greenhouse gasses covered by the Kyoto protocol The product label should never be removed from the unit. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
2014. Contain spilled material with sand, earth or other suitable absorbent material. Do not allow the refrigerant to enter drains, sewers or basements, as pockets of vapor can form. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
2.6.5 Further medical treatment Treat symptoms and carry out support therapy as indicated. Do not administer adrenaline or similar sympathomimetic drugs following exposure, due to the risk of cardiac arrhythmia. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
All units are supplied with the following control and protection devices: antifreeze protection sensor, high pressure switch with manual reset, low pressure switch with automatic reset, high pressure safety valve, compressor thermal overload protection, fans thermal overload protection. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
It’s used to ensure the best resistance against the atmospheric agents and the operation in aggressive enviroments. The frame is made of stainless steel AISI 304, self-supporting with removable panels to facilitate inspection and maintenance of internal components. All screws and rivets are in stainless steel. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
(1) Sound Power level according to ISO 961, fan with available static pressure 50 Pa. The refrigerant data may change without notice. It is therefore necessary to refer always to the silver label placed on the unit. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 15
2,05 2,15 Input power 0,19 0,22 0,34 0,35 B (Medium speed) Input current 0,85 1,00 1,65 1,72 Input power 0,18 0,21 0,33 C (Low speed) Input current 0,80 0,92 MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 17
It is recommended to move a single micro switch for each operating speed . The displacement of two or more micro switches may generate incorrect power supply voltages with malfunction or damage to the unit . MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
The units are designed to work in clean ambients and with the standard characteristics of the ambient air. It’s suitable not to install the unit in swimming pools or ambient with polluted and/or aggressive air. Contact the Company in case of necessity. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
(according to set parameters), switches the compressor off, while the fan remains in operation. At the end of the defrost cycle, there is a timer delay to allow condensate water to clear from the coil. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
4.3 Personal protective equipment When operating and maintaining the unit, use the following personal protective equipment listed below as required by law. Protective footwear. Eye protection. Protective gloves. Respiratory protection. Hearing protection. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Units can be lifted by using a forklift or, in alternative, using belts, being sure that the method of lifting does not dam- age the lateral panels and the cover. It is important to keep the unit horizontal at all time to avoid damages to the internal components. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
10 Pa 1 mm water column the fan, in any case never less than 35 mm. 4.9.1 How to remove the drip tray MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 23
MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Any reversal of polarity will result in the non-functioning unit. The supervision connectivity cable must be telephone one type 2x0, 25 mm contacting the assistance. TELEPHONE CABLE SERIAL INTERFACE CONNECTION CABLE WITH CARD ADAPTER UNITS MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
ASLE ASRI ASVE Left hand side Supply Vertical Supply (standard) Right hand side Supply Flexible connection Self-tapping screws ø 3,9 mm or 4,2 mm MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
It should be noted that the values in the numbered scale identify the desired The humidistat is supplied separately. For connection please refer to the wiring diagram supplied along with the unit. 115 mm MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
If opened, the main switch cuts the power off to any electric heater and antifreeze device supplied with the unit, includ- ing the compressor crankcase heaters. The main switch should only be disconnected for cleaning, maintenance or unit reparation. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
For powering the unit remove the front panel; use the appropriate cable gland present in the side panel and connect the power cord to the terminal block in the cabinet. After connecting all cable carefully close the front panel. Power supply Electric connections MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
The electric motors are directly connected to the fan; they are all at 3 speeds, with integrated thermal protection. Contact 31: Minimum speed Contact 30: Medium speed Contact 53: Maximum speed MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
• Before start up check that all panels are replaced in the proper position and locked with fastening screws. Do not modify internal wiring of the unit as this will immediately invalidate the warranty. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
In programming mode allows to scroll through the parameter codes or increases the values If press ed down for 5 seconds, it makes it possible to switch the unit on or off. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Humidity set, in the bottom line will appear the label SETI. Temperature set, in the bottom line will appear the label SETH. makes it possible to modify the set points; MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 33
If there is damage to the remote control or there is a faulty connection, failure of communication will be indicated in the display with the message “noL” (no link). MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Icon ON: the unit is on. Counter between two defrost cycles. Icon ON: the display shows the room temperature or hu- Not used. miditiy. Icon blinking: high pressure alarm is active. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 35
Unit equipped with electronic sensor Unit equipped with mechanical thermostat/hygrostat Unit in drip time after defrost Unit in drip time after defrost Unit equipped with electronic sensor Unit equipped with mechanical thermostat/hygrostat MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
The units are supplied with a very sophisticated control system with many other parameters that are not adjustable by the end user; these parameters are protected by a manufacturer password. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Durch unterhalb der Beckenwassertemperatur liegende Raumtemperaturen können schwerwiegende Bauwer- kschäden hervorgerufen werden! Die GmbH haftet nicht für Schäden, die durch falsche Einstellungen der Sollwerte für Temperatur und Feuchte sowie durch unzureichende Beheizung der Schwimmhalle hervorgerufen wurden! MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
The top case and dischar- ge line of compressor are usually at high temperature. Care must be taken when working in their surroundings. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 40
Check for freon leaks In order to carry out operations on the refrigerant, it is necessary to observe the European Regulation 517_2014, tionary refrigeration, air conditioning and heat pump equipment”. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
• When replacing the compressor following a burn out, it is advisable to wash the cooling system with appropriate products including a • When under vacuum do not switch on the compressor. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
2011/65/EU (RoHS), but if abandoned in the environment it has a negative impact on the ecosystem. that for which it was designed, as there is a risk of electric shock if used improperly. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Athi Hight room temperature. Replace faulty sensor Contact the Company Electrical heater thermal alarm cessary replace them. In (if present) ducted versions, check the pressure drop of the ducts. MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
75 - 100 MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 45
50 - 200 MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 46
75 - 100 (FARC) MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 47
HDA 150 - 200 - 250 (FARC) 50 - 200 (FARC) MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 48
MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 49
MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 50
MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 51
MTEC.6400.GB-F-1 Operation and maintenance manual HDA series English Rev. F 02-2021...
Page 52
HIDROS Srl Technical data shown in this booklet are not binding. The reference languages for the whole documentation are Italian and English. The other languages are to be considered only as guidelines.