3.3 General overview on the connectors in the heavy version
3.3.1 Mains connection ST 1
Mains connection at ST 1 with plug type SC 6-pole (5 + PE) CONINVERS and standard-cable with
A > 1,5 mm², e.g. H05VV-F1,5.
Choose a fuse according to the used cable. Additionally the KFM05A has to be grounded at the
earth bolt. A coupling can be ordered with SIEI-AREG-order-No. 166194.
3.3.2 Control connection ST2
Control connection via ST 2 type RC 16-polig (CONINVERS).
Pin assignment:
Pin 1 : PLC +24 V
Pin 2 : PLC 0 V
Pin 3 : Input 1
Pin 4 : Input 2
Pin 5 : Input 3
Pin 6 : Input 4
Pin 7 : Input 5 (Enabling)
Pin 8 : Output 1
Connection example see chapter 3.2.6. A coupling can be ordered with SIEI-AREG-order-No.
166163.
Art.-No.: 918 111e
SIEI-AREG GmbH
Gottlieb-Daimler-Straße 17/3
74385 Pleidelsheim Germany
Fon: +49 7144 89736 0
Pin 9 : Output 2
Pin 10 : Output 3
Pin 11 : Common OUT
Pin 12 : Brake (24 V)
Pin 13 : + 10 Vdc, 10 mA
Pin 14 : Input analog 1
Pin 15 : Input analog 2
Pin 16 : GND
Page 33 von 60
Rev. 09/14