The choice of the most suitable copper pipes must take into account the higher operating
pressure of the R32 gas compared to the old R22 and R407C refrigerants. Please refer to
the table below.
GAS TYPE
R32
R407C, R22
MINIMUM ROOM DIMENSIONS FOR R32 INSTALLATION
The area of the room in which R32 refrigerant air conditioner is installed cannot be less
than the minimum area specified in the table below, to avoid potential safety problems due
to out-of-limit of refrigerant concentration inside the room caused by leakage of refrigerant
from refrigeration system of the indoor unit.
The reference installation height for wall type air conditioners is 1.8 m. The floor/ceiling (in
floor installation) reference height is 0.6 m. Finally, cassettes and floor/ceiling (in ceiling
installation) reference height is 2.2 m.
1.3.

WEEE WARNINGS

-
Do not dispose of electronic equipment as household waste. Use
proper disposal facilities.
Contact your local council for more information about the collection
-
systems available.
lf electrical appliances are disposed of in landfills, hazardous
-
substances can leak out, contaminate water and reach the food chain,
affecting our health and wellbeing.
When old appliances are replaced by new ones, the retailer is legally
-
obliged to take back your old appliance far disposal free of charge.
PIPES
Radial thickness
(mm)
0.8
0.8
0.8
1.0
1.0
Pipes type 1/2H or H
MAX OPERATING PRESSURE
4.15 MPa
3.40 MPa
6
Type
Pipes type O
Pipes type O
Pipes type O
Pipes type O
Dimens. B
Dimens. A
flare nuts
flare (mm)
type 2 (mm)
9.1
17.0
13.2
22.0
16.6
26.0
19.7
29.0
24.0
36.0