The choice of the most suitable copper pipes must take into account the higher operating pressure of
the R32 gas compared to the old R22 and R407C refrigerants. Please refer to the table below.
GAS TYPE
R32
R407C, R22
MINIMUM ROOM DIMENSIONS FOR R32 INSTALLATION
The area of the room in which R32 refrigerant air conditioner is installed cannot be less than the
minimum area specified in the table below, to avoid potential safety problems due to out-of-limit of
refrigerant concentration inside the room caused by leakage of refrigerant from refrigeration system of
the indoor unit.
The height of installation of wall type air conditioners is 1.8 m. That one of the floor/ceiling type is 0.6
m, and finally cassettes one is 2.2 m.

1.3. WEEE WARNINGS

Do not dispose of electronic equipment as household waste. Use proper disposal
facilities. Contact your local council tor more information about the collection
systems available. lf electrical appliances are disposed of in landfills, hazardous
substances can leak out, contaminate water and reach the food chain, affecting
our health and wellbeing. When old appliances are replaced by new ones, the
retailer is legally obliged to take back your old appliance tor disposal free of
charge.
Radial thickness
(mm)
1/4"
0.8
3/8"
0.8
1/2"
0.8
5/8"
1.0
3/4"
1.0
PIPES
Type
Pipes type O
Pipes type O
Pipes type O
Pipes type O
Pipes type 1/2H or H
MAX OPERATING PRESSURE
4.15 MPa
3.40 MPa
6
Dimens. B
Dimens. A
flare nuts type
flare (mm)
2 (mm)
9.1
17.0
13.2
22.0
16.6
26.0
19.7
29.0
24.0
36.0