[ VIII Disassembly Procedure ]

2. Fan and fan motor

Be careful on removing heavy parts.
Electric shock hazard. Before performing any work, shut off the power supply.
OPERATING PROCEDURE
1. Remove the control box cover according to the procedure
in section [1]-1. Control box.
2. Removing the fan motor cable
(1) Disconnect the connector (CNMF1) from the control board.
(2) Remove the cable through the rubber bush.
3. Removing the bottom plate
(1) Remove the fifteen fixing screws on the bottom plate to
remove it.
4. Removing the fan case
(1) Remove the eight fixing screws on the fan case to remove it.
5. Removing the fan and fan motor
(1) Remove the earth lead of the motor from the motor base.
(Fig. 3)
The grounding wire of the motor wire is found only on the
P100, 125 and 140 models of units with motor
KMUC4E3MW. The model name of the motor is noted in the
nameplate on the fan motor casing.
(2) Remove the two fixing screws and attachment on the fan
motor (Fig. 4).
(3) Pull out the fan motor in the direction of the arrow (Fig. 4).
HWE1706A
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Exercise caution when removing heavy parts.