Page 1
Specification and Manual Customer: Description: Air Conditioner for Equipment Customer Part No.: Rev.: Delta Model No.: HEC1000AFR Rev.: Sample Date Code: Sample Issue Date: Please send one copy of this specification back after you signed approval for production pre-arrangement Approved by: Date: DELTA ELECTRONICS, INC.
The document is the exclusive property of Delta Electronics, Inc. it should not be distributed, reproduced, or any other format without prior permission of Delta.
Page 4
Part no.: Delta model no.: HEC1000AFR Warning: Installation work and electrical wiring should be done only by qualified personnel in accordance with all applicable codes, standards and national wiring regulations. Use this unit only in the manner intended by the manufacturer. If you have questions, please contact the manufacturer.
Page 5
Part no.: Delta model no.: HEC1000AFR Caution : Install the air conditioner on a wall or door strong enough to withstand the weight of the unit. Do not allow a child to mount onto the outdoor unit. Avoid placing any object on it.
Page 6
Specification for Approval Customer : Description : Air conditioner for Equipment with 1000 W Rated Cooling Capacity Customer P/N : Rev. : Delta model no. : HEC1000AFR Rev. : 00 Sample revision. : Date Code : Sample issue date :...
1. Product Instruction 1-1. General Description HEC1000AFR is a AC air conditioner with 115VAC power input, it is designed for NEMA4X sealed outdoor telecom cabinet to provide stable and optimum internal conditions for equipment and avoid hotspot inside the cabinet.
Page 8
Part no.: Delta model no.: HEC1000AFR Input Voltage Range 103~121/50Hz,105~127/60Hz Locked Rotor Current (60Hz) 15.9 Rated Current Minimum circuit ampacity (MCA) Maximum rating of overcurrent protective 11.7 device (MOP) Alarm Dry Contact Output Key Components Controller Built-in Smart Controller Fans...
Part no.: Delta model no.: HEC1000AFR 1-5. Configuration & Maintenance Make sure the air conditioner surface sealed with mounting flange to avoid water penetrates into shelter through mounting interface. It is suggested to use gaskets sticking on the mounting flange and seal the gap between flange and cabinet with silicone gel during installation.
Part no.: Delta model no.: HEC1000AFR Turn off the power before maintaining. Please turn off power and remove dry contact connector while non-operating for a long time. If any abnormal acoustic noise from air conditioner happened, please turn off the product and contact with customer services.
Part no.: Delta model no.: HEC1000AFR 2. Electrical Specification Power Supply & Alarm Connector & Indicator (1) AC Power Connect: Description Cable wire size 16 AWG 16 AWG 16 AWG (2) RS485 and J1 Connect: J1 Pin Name Description...
Page 14
Part no.: Delta model no.: HEC1000AFR • Normal: NC and COM dry contact output close • Alarms happening: NC and COM dry contact output open (Dry Contact will trigger when alarm happen except E2.6 and E5.1) (3) Panel operation: •...
Page 15
Part no.: Delta model no.: HEC1000AFR (4) Panel Operation Flowchart : ※ If no button is pressed, after 20 seconds, the panel will return to the Cabinet Temperature screen. ※ The default value of Password is 0001. SD card & Ethernet (Optional function): The controller used communication technology to remotely control, monitor, SD card 8 GB for logging data and alarm the cooling function of the ACU.
Part no.: Delta model no.: HEC1000AFR d2.03 Ambient temperature Display d2.04 Internal fan speed Display d2.05 External fan speed Display d2.06 Firmware version Display ※ d1.10 and d1.11 are option functions. Default is closed. ※ d2 layer is for system status information read only.
Page 19
Part no.: Delta model no.: HEC1000AFR Evaporator temperature sensor fault alarm E 3.2 Condenser temperature sensor fault alarm E 3.3 Ambient temperature sensor fault alarm E 3.4 Internal fan exception alarm(Only For DC Fan Project) Fan exception External fan exception alarm(Only For DC Fan Project)
Page 20
Part no.: Delta model no.: HEC1000AFR Fault Analysis and Processing Fault State Analysis of the Reasons Solutions 1. Check the power supply and Power on, and the 1. Power failure or no power. the electric circuit. cabinet temperature is 2. The target temperature is 2.
Thermal Solutions product family and manufactured by Delta Electronics, Inc., herein referred to as (“products”), will be free from defects in material and workmanship for a period of one (1) year from the date of shipment by Delta Electronics, Inc. This warranty covers repair or replacement of product at the sole discretion of Delta Electronics, Inc.
Page 22
All returns require a Return Material Authorization number (RMA #), regardless of reason for return, whether it be for warranty or out of warranty repair. Returns without an RMA # will be refused by Delta Electronics, Inc. Approval for return requests are at the sole discretion of Delta Electronics, Inc.
3. Quantity to be returned and a brief description of failure for each unit, if different. All returns to Delta Electronics, Inc must be securely packed, using original cartons if possible. All returns must have the RMA number visible on the outside of the carton.
Need help?
Do you have a question about the HEC1000AFR and is the answer not in the manual?
Questions and answers