Page 1
Air Conditioner for Equipment (Through Wall Mounting) Description : Customer Part No. : Rev.: HEC1000PB Delta Model No. : Rev : Sample Date Code: Sample Issue Date : SEP.15 2020 Please send one copy of this specification back after you...
The document is the exclusive property of Delta Electronics, Inc. it should not be distributed, reproduced, or any other format without prior permission of Delta. Specifications are subject to change without notice.
Page 5
Part no. : Delta model no. : HEC1000PB Warning: Installation work and electrical wiring must be done by qualified person(s) in accordance with all applicable codes, standards and national wiring regulations. Use this unit only in the manner intended by the manufacturer. If you have questions, please contact the manufacturer.
Page 6
Part no. : Delta model no. : HEC1000PB To avoid injury, do not touch the air inlet or aluminum fins of unit. Watch your steps at the time of fin cleaning or air conditioner inspection. Do not topple the air conditioner while moving or storage.
Page 7
Part no. : Delta model no. : HEC1000PB Specification for Approval Customer : Description : Air conditioner for Equipment with 1000 W Rated Cooling Capacity (Through Wall Mounting) Customer P/N : Rev. : Delta model no. : HEC1000PB Rev. : 02 Sample revision.
Product Instruction 1-1. General Description HEC1000PB is a DC air conditioner with 48 VDC power input, it is designed for IP55 sealed outdoor telecom cabinet to provide stable and optimum internal conditions for equipment and avoid hotspot inside the cabinet.
Page 9
Part no. : Delta model no. : HEC1000PB Power & Range Input Voltage Max. Operating DC Current 14.3 Alarm Dry Contact Output Key Components Controller Built-in Smart Controller Fans Delta High Efficiency Blowers Compressor Rotary, DC Page 9...
Part no. : Delta model no. : HEC1000PB 1-5. Configuration & Maintenance Make sure the air conditioner surface sealed with mounting flange to avoid water penetrates into shelter through mounting interface. It is suggested to use gaskets sticking on the mounting flange and seal the gap between flange and cabinet with silicone gel during installation.
Part no. : Delta model no. : HEC1000PB If any abnormal acoustic noise from air conditioner happened, please turn off the product and contact with customer services. The refrigerant is environmental friendly product of R134a. Little refrigerant leakage (< 5 g/ year) is allowed for application.
Part no. : Delta model no. : HEC1000PB Panel operation • A: Display: It will show the temperature inside the cabinet and system parametric setup. • B: LED indicator: Power: When the system power on and the LED will light in green.
Page 16
Part no. : Delta model no. : HEC1000PB Allow reverse voltage: 42 ~ 58 VDC Short Ckt: If compressor UVW short for any both phase the compressor will not operate. Compressor H/T protection ≧ 105 comp Eva L/T protection <...
Part no. : Delta model no. : HEC1000PB 3. Environmental Condition 3-1. Operating Temperature -10 °C ~ +55 °C (14 °F ~ 131 °F) 3-2. Storage Temperature -40 °C ~ +70 °C (-40 °F ~ 158 °F) 3-3. Operation Humidity...
Part no. : Delta model no. : HEC1000PB 6. Accessory Power and Alarm Cable Description Cable wire size 14 AWG PIN1(+) PIN2(-) -48 V 14 AWG 7. Parameters Table 7-1. System Setup Item System Parameter Default Range d1.1 System Version d1.2...
Part no. : Delta model no. : HEC1000PB 7-2. Alarm Logs & Fault Processing Alarm Indicators Flash Times LV1 Alarm LV2 Alarm Alarm Code (Power Led) Compressor 3-min Protection Compressor Power Protection Low-Temp Startup Protection Eva Temperature Protection Comp-out Temperature Protection...
Page 20
Part no. : Delta model no. : HEC1000PB Fault Analysis and Processing Fault State Analysis of the Reasons Solutions 1. Check the power supply and the electric 1. Power failure or no power. Power on, and the cabinet circuit. temperature is too high 2.
Part no. : Delta model no. : HEC1000PB 8. Installation Notice Check the surrounding obstacles to make sure the product get enough space for air circulate. * Recommended “a” keeps 1.0 meter at least Space tight causes air re0circulation. Reduce cooling performance potentially keeps space as wide as possible 9.