#57736
Connections, displays and control elements:
Digital IOs:
Network:
Power supply:
Output supply
Galvanische Trennung:
Conections:
Displays:
Data transfer:
Protocols:
Response times:
Housing and other data:
Housing:
Enclosure rating:
Weight:
Storage temperature:
Operating temperature:
Permissible relative
humidity:
60
16 channels selectable input/output operation
As output: 12-24V DC / 500mA per channel
Total fuse protection for all outputs 3A
As input: max. 30V DC
Switching threshold 9.5V +/- 1V
„On" current = 2.2 mA
Integrated 32-bit pulse counter
10/100BaseT autosensing
12 ... 24V DC (approx. 100mA@24V)
12 ... 24V DC
Digital IOs - network: min. 1000 V
3 x 12x screw terminal block for IOs
1 x 11x screw terminal block for IOs
1 x 4x screw terminal block for power
1 x RJ45 für Netzwerk
Status LEDs for network
Error LEDs for system and application
8 LEDs for digital status
TCP- und UDP-Sockets, Client und Server
SNMP inkl. Traps, SMTP E-Mail-Versand
OPC-DA, OPC UA, Modbus-TCP, Inventarisierung
Datatrafic: typ. 40 - 80ms
Plastic housing 90 x 45 x 56 mm (lxbxh)
IP20
ca. 250 g
-25°C .. 70°C
0°C .. 50°C
5..95% RH (non-condensing)