Lenze ESMD Series Manual

Lenze ESMD Series Manual

Advertisement

These Instructions
contain important technical data and describe installation,
operation and commissioning of the smd frequency inverter.
are only valid for smd frequency inverters with software rev 14
(see drive nameplate).
Please read the Instructions before commissioning.
Commissioning using the Lenze settings
1.
Read the Safety Notes
2.
Installation
3.
Wiring of power and control connections
Important: Observe minimum wiring requirements!
4.
Power up
Display: OFF
OFF
OFF
OFF
OFF
5.
Setpoint selection through potentiometer
6.
Set terminal 28 to HIGH and terminal E2 to LOW.
Response: Motor accelerates to setpoint with CW rotation
Display shows output frequency in Hz, e.g. 50
7.
If necessary, optimise settings
Faults during commissioning/operation
4 x M4
A
B
1.2 Nm
C
10 lb-in
4 x M6
2.8 Nm
D
24 lb-in
smd402
Type
ESMD...
371L4TXA
751L4TXA
112L4TXA
152L4TXA...222L4TXA
302L4TXA
402L4TXA...552L4TXA
552L2TXA...752L2TXA
752L4TXA...113L4TXA
113L2TXA...153L2TXA
153L4TXA...223L4TXA
L
50 50
50 50 . 0 0 0 0 0
a1
a
a [mm]
a1 [mm]
b [mm]
93
84
146
93
84
146
93
84
146
114
105
146
114
105
146
114
105
146
146
137
197
195
183
248
AC Technology Corporation • 630 Douglas Street • Uxbridge, MA 01569 • USA
+1 (508) 278-9100
smd frequency inverter
c
b1 [mm]
b2 [mm]
c [mm]
128
17
100
128
17
120
128
17
146
128
17
133
128
17
171
95
17
171
140
17
182
183
23
203
L
see
2
4
5
8
s1
s1
s1 [mm]
s2 [mm]
15
50
15
50
15
50
15
50
15
50
15
50
30
100
30
100
smd401
m [kg]
0.6
0.8
1.0
1.4
1.7
1.8
3.2
6.4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ESMD Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Lenze ESMD Series

  • Page 1 14 (see drive nameplate). • Please read the Instructions before commissioning. smd401 Commissioning using the Lenze settings Read the Safety Notes Installation Wiring of power and control connections Important: Observe minimum wiring requirements!
  • Page 2: Safety Information

    Safety information General Some parts of Lenze controllers (frequency inverters, servo inverters, DC controllers) can be live, moving and rotating. Some surfaces can be hot. Non-authorized removal of the required cover, inappropriate use, incorrect installation or operation, creates the risk of severe injury to personnel or damage to equipment.
  • Page 3: Technical Data

    Technical data Type Power Mains Output Current for 60 s Voltage, frequency Current [kW] ESMD552L2TXA 3/PE 230/240 V ESMD752L2TXA (180 V -0%…264 V +0%) ESMD113L2TXA 50/60 Hz (48 Hz -0%…62 Hz +0%) ESMD153L2TXA 400 V 480 V 400 V 480 V 400 V 480 V 400 V...
  • Page 4: Installation

    +12 V DC - 0 % smd403 … +30 V DC + 0 % Terminal Data for control connections (printed in bold = Lenze setting) RS-485 serial communication input Modbus or LECOM RS-485 serial communication input Reference potential Analog input input resistance: >50...
  • Page 5: Parameter Setting

    Programming = Modbus/keypad Code c40 10 Analog input (terminal 8) Control = Modbus Programming = Modbus/keypad 11 Code c40 Load Lenze setting No action/loading complete Caution: C02 = 1 overwrites all settings Load (only possible with OFF OFF or Inh Inh )
  • Page 6 0...20 mA 4...20 mA Voltage - DC injection 50.0 brake (DCB) Fixed setpoint 1 (JOG 1) 20.0 {Hz} Lenze setting: active at E1 = HIGH Fixed setpoint 2 (JOG 2) 30.0 {Hz} Fixed setpoint 3 (JOG 3) 40.0 {Hz} Frequency setpoint...
  • Page 7 Parameter Setting Code Possible Settings IMPORTANT Name Lenze Selection C99 Software version Display, format x.yz Holding time - automatic Automatic motor braking below 0.1 Hz by means of DC injection brake (Auto- motor DC current for the entire holding time 0.0 = not active...
  • Page 8: Troubleshooting And Fault Elimination

    Error Cause Remedy Data not valid for controller • Use EPM providing valid data Data on EPM not valid • Load Lenze setting Data error EPM error EPM missing or defective Power down and replace EPM Digital inputs not E1...E3 assigned with the same digital...