Specifications

2.3 Specifications
 AC Power - TB1
APS2-6R - 120VAC, 50/60 Hz, 2.9A max
APS2-6RE - 220-240 VAC, 50/60 Hz, 1.5A max
Earth Ground - Connects to chassis or earth ground terminal on main power supply. If two units are connected,
the second unit connects to earth ground on the previous AP2S-6R in the chain.
Supervised
Wire Size: 12-14 AWG (3.31-2.08 mm
 24 VDC Secondary Input Power (Battery Connection) - TB3
41 mA DC standby current
Supervised
Wire Size: 12-14 AWG (3.31 - 2.08 mm
Batteries (2) must be installed in the same or closely coupled separate cabinet which is to be mounted up to 20 feet
(6.096 m) away from the APS2-6R, in the same room. When a separate cabinet is used, wiring must be in conduit.
 24 VDC Output Power - TB2
Total 6A (4A continuous) power
Two (2) power-limited circuits - 3A @ 24 VDC (20V - 26.39V) each
Supervised by an end-of-line listed power supervision relay
Wire Size: 12-18 AWG (3.31 - 0.82mm
Special applications- refer to the Device Compatibility Document
 24 VDC Output Power - J9
Total 6A (4A continuous) power
One (1) non-power-limited circuit - 6A @ 24 VDC (20V - 26.39V)
Supervised by the XPIQ transponder
Cable: P/N 75121 only
Special applications- refer to Section 3.3.1
 Trouble Supervision Bus - J3, J4
J3 output, J4 input
Form-A contact (open collector)
Cable: P/N 71033
For trouble supervision, connect cable p/n 71033 from J3 to a trouble bus connection of a fire panel, main power
supply or J4 of another APS2-6R. Sections 3.3.3, 3.3.4, and A.1.1
 Fuse - F2
F2-Battery Supervision: 32 VAC, 10A, MINI® Fast-Acting Automotive Blade Fuse (serviceable, replacement
P/N 12067)
 Loss of AC Indication - TB4 (UL 864 9th Edition Applications)
Monitored by FMM-1 or equivalent monitor module over the SLC
Wire Size: 12-18 AWG (3.31 - 0.82mm
Immediate indication provided by the relay contacts for local notification. The FACP follows its own programmed
schedule for failure reporting.
 Combining Troubles - JP4 (UL 864 8th Edition Applications)
Installation of the shunt across jumper JP4 provides compatibility with retrofit applications by combining all existing
troubles. JP1 and JP2 can be used to delay AC trouble reporting. See Section 3.4 for more information.
APS2-6R/E Instruction Manual — P/N 53232:B 2/26/2014
2
) with 600 VAC insulation
2
)
NOTE: The APS2-6R is not equipped with a battery charger. Batteries are charged by the
system power supply.
2
)
NOTE:
The APS2-6R can provide up to 6A for releasing applications, limited by the
FCM-1-REL.
NOTE: The combined total of all three output circuits is 6A during a fire alarm or 4A of
continuous power.
2
), UL1015, stranded.
Overview
9