Appendix B: Ul 864 8Th Edition Configurations; B.1: Afp-200; B.1.1: Connecting The Aps2-6R To The Afp-200 - Honeywell NOTIFIER APS2-6R/E Instruction Manual

Table of Contents

Advertisement

Appendix B: UL 864 8th Edition Configurations

The APS2-6R does not come equipped with a battery charger. Therefore, it must be connected to the control panel's
main power supply. This section details wiring for UL 864 8th Edition applications. All wiring must comply with
typical UL power-limited wiring requirements detailed in Section 3.2 and illustrated in Figure A.1.
B.1 AFP-200
The APS2-6R is mounted behind the control panel in the AFP-200 backbox. See "In an AFP-200 Cabinet" on
page 11 for instructions on how to mount the APS2-6R in the backbox.
B.1.1 Connecting the APS2-6R to the AFP-200
1.
Connect trouble output from J3 on the APS2-6R to J11 on the AFP-200.
2. Place shunt across both pins of JP4 on the APS2-6R.
3. Connect primary power from TB7 on the AFP-200 to terminal block TB1 on the APS2-6R, using wire nuts to
make the connections. Make sure to properly ground the unit to the backbox.
4. Cut the battery cable supplied with the AFP-200 into two pieces.
5. Connect the batteries to TB3 on the APS2-6R. Use wire nuts to attach one half of the battery cable to 18 AWG
wire.
6. Connect secondary power from TB3 on the APS2-6R to terminal block J3 (+ and -) on the AFP-200 using the
second piece of battery cable.
20
WARNING: Risk of electrical shock
!
Remove all power sources to equipment while connecting electrical components. Leave the
external, main power breaker OFF until installation of the entire system is complete. To reduce
the risk of electric shock make sure to properly ground the unit. Apply and test AC power
before connecting batteries.
WARNING: Risk of equipment damage
!
Several sources of power can be connected to the control panel and/or power supply. Before
servicing the control panel, disconnect all sources of input power including the battery. While
energized, the control panel and associated equipment can be damaged by removing and/or
inserting cards, modules, or interconnecting cables.
NOTE: When two conductors are connected to the same terminal, the same gauge wire must
be used.
WARNING:
!
Be sure to finish installation before applying power. Test AC power before continuing.
APS2-6R/E Instruction Manual — P/N 53232:B 2/26/2014

Advertisement

Table of Contents
loading