Appendix A: UL 864 9th Edition Configurations

The APS2-6R does not come equipped with a battery charger. Therefore, it must be connected to the control panel's
main power supply. This section details wiring for UL 864 9th Edition applications. All wiring must comply with
typical UL power-limited wiring requirements detailed in Section 3.2 and illustrated in Figure A.1.
A.1 NFS2-3030
The APS2-6R must be mounted to the CHS-4/L chassis in the CAB-3/4 Series backbox. See "In a CAB-3/4 Series
Backbox" on page 11.
A.1.1 Connecting to the AMPS-24 and NFS2-3030
1. Connect trouble output from J3 on the APS2-6R to the J5 Trouble Bus connection on the CPU2-3030.
2. Connect AC Fail supervision relay output from TB4 on the APS2-6R to an FMM-1 or equivalent monitor
module on the SLC (Signaling Line Circuit).
3. Connect primary power from TB1 on the APS2-6R to TB1 on the AMPS-24.
4. Connect AC power to TB1 on the AMPS-24. Make sure to properly ground the unit to the backbox.
5. Connect batteries to TB3 on the AMPS-24.
6. Connect secondary power from TB3 on the APS2-6R to TB3 on the AMPS-24.
7. Attach battery interconnect cable.
APS2-6R/E Instruction Manual — P/N 53232:B 2/26/2014
WARNING: Risk of electrical shock
!
Remove all power sources to equipment while connecting electrical components. Leave the
external, main power breaker OFF until installation of the entire system is complete. To reduce
the risk of electric shock make sure to properly ground the unit. Apply and test AC power
before connecting batteries.
WARNING: Risk of equipment damage
!
Several sources of power can be connected to the control panel and/or power supply. Before
servicing the control panel, disconnect all sources of input power including the battery. While
energized, the control panel and associated equipment can be damaged by removing and/or
inserting cards, modules, or interconnecting cables.
NOTE: When two conductors are connected to the same terminal, the same gauge wire must
be used.
WARNING:
!
Be sure to finish installation before applying power. Test AC power before continuing.
NOTE: If your AMPS-24 does not look like the one pictured in Figure A.1, but looks like the
one pictured in Figure B.6, connect secondary power from TB3 on the APS2-6R to TB4 and
TB5 on the AMPS-24. Note that the main power output on this AMPS-24 is Non-Power-
Limited.