Carrier 48TC**16 Installation Instructions Manual page 44

Single package rooftop gas heating/electric cooling unit with puron (r-410a) refrigerant
Hide thumbs Also See for 48TC**16:
Table of Contents

Advertisement

Completing Installation of Return Air Smoke Sensor:
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig. 85. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-
wards and the sampling tube connection is on the bot-
tom. See Fig. 86.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the ex-
haust tube is on the top. See Fig. 86.
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Fig. 85 - - Return Air Detector Shipping Position
Controller
Screws
Flexible
Exhaust
Tubes
Sampling Tube
C10331
Fig. 86 - - Return Air Sensor Operating Position
Additional Application Data —
Refer to Catalog No. HKRNKA- - 1XA for discussions on
additional control features of these smoke detectors
including multiple unit coordination.
44
Sampling Tube
C10332