Penn F261 Series Installation Manual

Penn F261 Series Installation Manual

Hide thumbs Also See for F261 Series:

Advertisement

Quick Links

Applications
Important:
• Do not install or use this F261 Series Flow Switch in or near environments where corrosive
substances or vapors could be present. Exposure of the F261 Series Flow Switch to corrosive
environments may damage the device's internal components and will void the warranty.
• Do not use F261 Series Flow Switches where the fluid in the pipes drops below the fluid's
freezing point, causing an internal freeze-up.
Important: Use this F261 Series Flow Switch only as an operating control. Where failure
or malfunction of the flow switch could lead to personal injury or property damage to the
controlled equipment or other property, additional precautions must be designed into the
control system. Incorporate and maintain other devices, such as supervisory or alarm systems
or safety or limit controls, intended to warn of or protect against failure or malfunction of the
flow switch.
Important: Utiliser ce F261 Series Flow Switch uniquement en tant que dispositif de
régulation. Lorsqu'une défaillance ou un dysfonctionnement du flow switch risque de
provoquer des blessures ou d'endommager l'équipement contrôlé ou un autre équipement, la
conception du système de contrôle doit intégrer des dispositifs de protection supplémentaires.
Veiller dans ce cas à intégrer de façon permanente d'autres dispositifs, tels que des systèmes
de supervision ou d'alarme, ou des dispositifs de sécurité ou de limitation, ayant une fonction
d'avertissement ou de protection en cas de défaillance ou de dysfonctionnement du flow
switch.
Risk
This product is made of a copper alloy, which contains lead. The product is therefore not to be used on
drinking water.
The F261 Series Flow Switches respond to fluid flow in lines carrying water, ethylene glycol, or
other nonhazardous fluids. These models also work in applications with swimming pool water and
lubricating oils.
F261 Series Standard Flow Switches use a variety of paddle sizes to respond to fluid flow rates in
applications with 1 inch trade size (or greater) pipe.
F261 Series Low Flow Switches respond to low fluid flow rates in applications with 1 inch trade size
(or less) pipe.
A low-energy model with gold-plated contacts provides improved electrical performance in low-
voltage, low-current circuits to operate small relays, solenoid valves, and electronic control circuits.
Part No. 24-7664-2969 Rev. E
2019-03-26
F261 Series Flow Switches Installation
WARNING
Guide
F261KEH, F261MEH, F261KFH, F261MFH

Advertisement

Table of Contents
loading

Summary of Contents for Penn F261 Series

  • Page 1 Exposure of the F261 Series Flow Switch to corrosive environments may damage the device’s internal components and will void the warranty. • Do not use F261 Series Flow Switches where the fluid in the pipes drops below the fluid’s freezing point, causing an internal freeze-up.
  • Page 2: Installation

    Installation F261 Series Standard Flow Switches are packaged with 1 in., 2 in., 3 in., and 6 in. stainless steel flow paddles along with a paddle screw and lock washer. See Table 2 for replacement parts. Dimensions Figure 1: Dimensions for F261 Standard Flow Switch, in. [mm]...
  • Page 3 Adjust the flow paddles to the size of the pipe used. Install the large flow paddle, if needed. Trim the flow paddle at the arc corresponding to the pipe size. See Figure 3, Figure 4, Figure 6, and Table F261 Series Flow Switches Installation Guide...
  • Page 4 1 in. 1-1/4 in. 2 in. 1-1/2 in. 2 in. 2 in. 2 in. 2-1/2 in. 3 in. 3 in. 3 in. 4 in. 6 in. 5 in. 6 in. 6 in. 6 in. F261 Series Flow Switches Installation Guide...
  • Page 5 Important: To avoid damaging the switch, do not tighten the switch to the tee by grasping the switch enclosure. Use only the wrench flats provided. Mount the F261 Series Flow Switches using the following guidelines: • Install the switch so that the enclosure and interior are accessible.
  • Page 6: Location Considerations

    Example: Use a 2 in. x 2 in. x 1 in. tee for a 2 in. pipe. If a standard 2 in. x 2 in. x 2 in. tee is used, install a face or hex bushing in the top opening to reduce the top opening to 1 in. Location Considerations Figure 7: Flow Direction for Vertical Mounting F261 Series Flow Switches Installation Guide...
  • Page 7 See Figure 9. Figure 9: Angle Allowed Note: Do not subject the flow switches to water hammer. Use a suitable water hammer arrester if a fast-closing valve is located downstream of the switch. See Figure 10. F261 Series Flow Switches Installation Guide...
  • Page 8 • Do not exceed the control’s electrical ratings. Exceeding the control’s electrical ratings can result in permanent damage to the control and void any warranty. The F261 models have three color-coded terminals. Red is common. See Figure 11 and Table 3 for switch action. F261 Series Flow Switches Installation Guide...
  • Page 9: Setup And Adjustments

    CAUTION Risk of Property Damage. Do not attempt to change sealed settings. Attempted adjustment may damage the control or cause loss of calibration or other property damage. F261 Series Flow Switches Installation Guide...
  • Page 10 • if the lever fails to click every time when returning to the original position, then the control’s flow rate is set below the factory-set minimum value. Turn the adjustment screw clockwise to raise the flow rate required to activate the switch. See Figure 12. F261 Series Flow Switches Installation Guide...
  • Page 11 76.0 (1.93) 111 (25.2) 135 (30.7) 400 (90.8) (Close R to B) Table 6: GPM (L/Min) Required to Actuate F261 Series Low Flow Switches Pipe Size 1/2 x 1/2 in. Female 3/4 x 3/4 in. Female 3/4 x 3/4 in. Female...
  • Page 12: Operation

    Figure 14: Pressure Drop versus Flow Rate, F261 Series Low-Flow Switches (F261KEH-V01C, F261MEH-V01C, F261KFH-V01C, F261MFH-V01C) Operation The flow switch responds to pressure exerted on the fluid paddle by the flowing fluid. A range adjustment screw adjusts the rate of the flow required to activate the switch. For flow rates, see Table 4 through Table 6.
  • Page 13: Troubleshooting

    Control does not switch on flow Check for a cracked or broken paddle. Replace the paddle, if increase. necessary. F261 Series Fluid Flow Switches Technical Specifications Table 9: F261xxH Series Standard Controls Electrical Ratings UL60730/UL1059 EN60730...
  • Page 14 • 302°F (150°C) permitted when ambient air is less than 140°F (60°C) and media is less than 249°F (121°C) Vessel Pressure F261 Fluid Flow Switch: 290 psi (20 Bar) Table 13: F261 Series Fluid Flow Switches Technical Specifications Specification Description Switch...
  • Page 15: North American Emissions Compliance

    Table 13: F261 Series Fluid Flow Switches Technical Specifications Specification Description Conduit Connection One 7/8 in. (22 mm) hole for 1/2 in. trade size (or PG16) conduit Pipe Connector Standard: 1 in. 11-1/2 NPT Threads Low-Flow: 1/2 in. x 1/2 in. Female NPTF 3/4 in.
  • Page 16 Canada This Class (B) digital apparatus meets all the requirements of the Canadian Interference-Causing Equipment Regulations. Cet appareil numérique de la Classe (B) respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada. © 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice.