Tech Settings
The compressor short cycle delay
protects the compressor from
Compressor
short cycling. This feature will not
Short Cycle
allow the compressor to be turned
Delay
on for 5 minutes after it was last
turned off.
The differential setting, often
called cycle rate or anticipation,
is adjustable. A smaller differential
Cooling
setting will cause more frequent
Differential
cycles and a larger differential
or Swing
setting will cause fewer cycles.
The differential setting often
called cycle rate or anticipation, is
Heating
adjustable. A smaller differential
Differential
setting will cause more frequent
or Swing
cycles and a larger differential
setting will cause fewer cycles.
TECHNICIAN SETUP MENU
LCD Will Show Adjustment Options
Next step
Selecting ON will not allow the
compressor to be turned on for
5 minutes after the last time the
compressor was on. Select OFF to
remove this delay.
Prev step
The cooling differential setting
Next step
is adjustable from 0.2° to 2°. For
example: A differential setting
of 0.5° will turn the cooling on
at approximately 0.5° above the
setpoint and turn the cooling off
at approximately 0.5° below the
Prev step
setpoint.
The heating differential setting is
Next Step
adjustable from + 0.2° to + 2°.
For example: A differential setting
of 0.5° will turn the heating on
at approximately 0.5° below the
setpoint and turn the heating off
at approximately 0.5° above the
Prev step
setpoint.
Default
ON
0.5
0.4
15