APPENDIX A - LOCAL DISPLAY AND CCN TABLES

ITEM
RUN STATUS
VIEW
Auto View of Run Status
HVAC
HVAC Mode Status
OCC
Currently Occupied
SAT
Supply Air Temperature
ALRM
Current Alarms & Alerts
TIME
Time of Day
VERS
Software Version Numbers
MBB
CESR131459--- xx--- xx
ECB
CESR131249--- xx--- xx
AUX
CESR131333--- xx--- xx
MARQ
CESR131171--- xx--- xx
MODE
Control Modes
SYS
Unit operation disabled
Unit operation enabled
Service test enabled
HVAC
HVAC Operation Disabled
Ventilation (fan--- only)
Cooling
Unoccupied Free Cooling
Heating
HV.DN
Remote HVAC Mode Disable
EFF.C
Cool Setpoint in Effect
EFF.H
Heat Setpoint in Effect
OCC
Currently Occupied
T.OVR
Timed Override in Effect
LINK
Linkage Active
D.LMT
Demand Limit In Effect
C.LOC
Compressor OAT Lockout
H.LOC
Heat OAT Lockout
E.LOC
Econo Cool OAT Lockout
COOL
Cooling Status
DMD.C
Cooling Demand
SA.CP
Supply Air Control Point
SASP
Cool Supply Air Setpoint
SR.CD
Cool Demand SASP Reset
SR.RH
Dehumidifying SASP Reset
F.SPD
Commanded Fan Speed
CMP .A
Compressor A Feedback
TG.A
Compressor A Timeguard
CAPC
Compressor Capacity
MAX.C
Max Compressor Capacity
MIN.C
Min Compressor Capacity
LMT.C
Max Capacity In Effect
SST.A
Sat. Suction Temp A
SSP .A
Suction Pressure A
SCT.A
Sat. Condenser Temp A
SCP .A
Condenser Pressure A
OFC.1
Outdoor Fan 1 Relay
HEAT
Heating Status
DMD.H
Heating Demand
AVL.H
Available Heating Stages
REQ.H
Requested Heating Stages
MAX.H
Max Allowed Heat Stages
LMT.H
Max Heat Stage In Effect
F.SPD
Commanded Fan Speed
HT.1
Heat Stage 1 Relay
TG.H1
Heat Stage 1 Timequard
HT.2
Heat Stage 2 Relay
TG.H2
Heat Stage 2 Timequard
ECON
Economizer Status
EC.CP
Econo Commanded Position
EC.AP
Econo Actual Position
EC.MP
Min Position in Effect
IAQ.S
IAQ Level (switch)
IAQ
IAQ Level (sensor)
OAT
Outdoor Air Temperature
ENTH
Outdoor Enthalpy Switch
OAQ
OAQ Level (sensor)
PE.1
Power Exhaust 1 Relay
PE.2
Power Exhaust 2 Relay
HRS
Component Run Hours
A1
Compressor A1 Run Hours
CCH
Crankcase Htr Run Hours
IDF
Indoor Fan Run Hours
OFC.1
Outdoor Fan 1 Run Hours
HT.1
Heat Stage 1 Run Hours
HT.2
Heat Stage 2 Run Hours
PE.1
Power Exhaust1 Run Hours
PE.2
Power Exhaust2 Run Hours
ALRM
Alarm Relay Run Hours
Table 27 — MODE - RUN STATUS
EXPANSION
RANGE
1=Disabled
2=Fan Only
3=Cool
4=Heat
Yes/No
xxx..x
xx
xx.xx
(xx--- xx in
table)
Yes/No
xxx.x
xxx.x
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
Yes/No
xxx.x
xxx.x
xxx.x
xxx.x
xxx.x
xxx
On/Off
xxx
xxx
xxx
xxx
xxx
xxx.x
xxx.x
xxx.x
xxx.x
On/Off
xxx.x
x
x
x
x
xxx
On/Off
xxx
On/Off
xxx
xxx
xxx
xxx
High/Low
xxxx
xxx.x
High/Low
xxxx
On/Off
On/Off
xxxxx.xx
xxxxx.xx
xxxxx.xx
xxxxx.xx
xxxxx.xx
xxxxx.xx
xxxxx.xx
xxxxx.xx
xxxxx.xx
CCN
UNITS
TABLE/SUB--- TABLE
STATUS DISPLAY
(VIEW = Display only)
HVACMODE
OCCUPIED
dF
SAT_DISP
ALRMALRT
hh.mm
TIMECOPY
VERSIONS
MODEL_NUMBER_01
MODEL_NUMBER_02
MODEL_NUMBER_03
MODEL_NUMBER_04
MODEDISP
SYS_MODE_TEXT1
SYS_MODE_TEXT2
(table only)
SYS_MODE_TEXT3
(table only)
HVACMODE_TEXT_1
HVACMODE_TEXT_2
(table only)
HVACMODE_TEXT_3
(table only)
HVACDOWN
CSP_EFF
HSP_EFF
OCCUPIED
MODETOVR
MODELINK
MODEDMDL
COMPLOCK
HEATLOCK
ECONLOCK
COOLDISP
^F
COOL_DMD
dF
SA_CTLPT
dF
SASP
^F
CD_RESET
^F
RH_RESET
%
FANSPEED
COMP_A
sec
TIMGD_A
%
CAPACITY
%
MAX_CAPC
%
MIN_CAPC
%
CAPLIMIT
dF
SST_A
psig
SSP_A
dF
SCT_A
psig
SCP_A
OFC_1
HEATDISP
^F
HEAT_DMD
AVLHSTGS
REQHSTGS
MAXHSTGS
HSTGLIMT
%
FANSPEED
HEAT_1
sec
TIMGD_H1
HEAT_2
sec
TIMGD_H2
ECONDISP
%
ECONOCMD
%
ECONOPOS
%
MIN_POS
IAQIN
ppm
IAQ
dF
OA_TEMP
ENTHALPY
ppm
OAQ
PE_1
PE_2
STRTHOUR
hours
HR_A1
hours
HR_CCH
hours
HR_IDF
hours
HR_OFC_1
hours
HR_HTR_1
hours
HR_HTR_2
hours
HR_PE_1
hours
HR_PE_2
hours
HR_ALM
68
CCN WRITE
CCN POINT
STATUS
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible
forcible

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0548pd0650pd0550pd06