Carrier 48/50PD05 User Manual page 57

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron(r--410a)refrigerant and comfortlink 1.x controls
Table of Contents

Advertisement

Space Temperature Sensor (T- - 58)
The T- -58 space temperature sensor (part no. 33ZCT58SPT) is a
field-installed accessory. The T- -58 sensor communicates with the
ComfortLink™ controller, providing space temperature, heating
and cooling set points, and mode operation information.
Refer to the T- -58 installation instructions for information on
installing and configuring the T- -58 sensor.
BUILDING SUPERVISOR
NETWORK
OPTIONS
REMOTE
AUTODIAL
CCN SITE
GATEWAY
NON CARRIER
HVAC
EQUIPMENT
COMFORT
CONTROLLER
CCN BUS
ROOFTOP
UNIT
CL
ROOFTOP
UNIT
CL
TERMINAL
SYSTEM
MANAGER
CL
ROOFTOP
UNIT
AIR DISTRIBUTION-DIGITAL AIR VOLUME CONTROL (DAV)
Fig. 25 - - CCN System Architecture
Each T- -58 sensor must have a unique address on the CCN. Each
T- -58 sensor must also be configured with the address of the unit
control it is communicating to.
Space Temperature Sensor Averaging
See Fig. 26 for space temperature averaging with T- -55 sensors
only. If the use of one T- -56 sensor is required, refer to Fig. 27.
ROOFTOP
CL
ROOFTOP
UNIT
CL
HEATING/COOLING UNITS
TCU
TCU
DAV AIR
DAV AIR
TERMINAL
TERMINAL
57
UNIT
LEGEND
CCN -- Carrier Comfort Networkr
CL -- ComfortLinkt Controls
DAV -- Digital Air Volume
HVAC -- Heating, Ventilation, and
Air Conditoning
TCU -- Terminal Control Unit
TO
ADDITIONAL
TERMINALS
TCU
DAV FAN
POWERED
MIXING
BOX
C07030