Indicate Unit Settings Below - Carrier 48/50PD05 User Manual

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron(r--410a)refrigerant and comfortlink 1.x controls
Table of Contents

Advertisement

CONTROL SET POINT AND CONFIGURATION LOG
Model Number: _____________________________
Serial Number: ______________________________
Date: ______________________________________
Technician: _________________________________
Control Type:
Thermostat/T55 Space Temp./T- -56 Space Temp./T- -58 Space Temp.
Set Points:
Cooling
Heating
ITEM
CONFIGURATION
DISP
Display Configuration
METR
Metric Display
LANG
Language Selection
PROT
Password Enable
PSWD
Service Password
TEST
Test Display LEDs
UNIT
Unit Configuration
S.DLY
Startup Delay
OC.FN
Fan On When Occupied
IDF.F
Shut Down on IDF Failure
FS.MX
Supply Fan Maximum
Speed
FS.MN
Supply Fan Minimum Speed
FS.VM
Vent Mode Fan Speed
FN.SW
Fan Status Switch
FL.SW
Filter Status Switch
FS.SW
Fire Shutdown Switch
RM.SW
Remote Occupancy Switch
RH.S
RH Sensor on OAQ Input
RH.SW
Space Humidity Switch
TCS.C
Temp Cmp Strt Cool Factr
TCS.H
Temp Cmp Strt Heat Factr
COOL
Cooling Configuration
MIN.C
Min Compressor Capacity
FS.CD
Fan Speed Control Demand
MRT.C
Compressor Min On Time
MOT.C
Compressor Min Off Time
RST.C
Runtime to Reset Strikes
FOD.C
Fan--- off Delay, Mech Cool
CS.A1
Current Sensing A1
C.LO
Compressor Lockout Temp
ALM.N
Alert Each Strike
SAT
Supply Air Temperature
SASP
Cool Supply Air Setpoint
SA.MU
SASP Maximum Reset Up
SA.MD
SASP Maximum Reset
Down
SAT.U
Minimum SAT Upper Level
SAT.L
Minimum SAT Lower Level
SST
Low Suction Control
SST.O
Suction OK Temperature
SST.1
Low Suction --- Level 1
SST.2
Low Suction --- Level 2
SST.3
Low Suction --- Level 3
PSI.D
Ckt A Minimum Pressure
OFC
Outdoor Fan Control
1.MXP
Fan Lev1 Max Pressure
2.MNP
Fan Lev2 Min Pressure
2.ON
Fan Lev2 On Temperature
2.OFF
Fan Lev2 Off Temperature

INDICATE UNIT SETTINGS BELOW

Occupied: _______________
Occupied: _______________
Table 65 — MODE - CONFIGURATION
EXPANSION
RANGE
On/Off
0=English
1=Spanish
2=French
3=Portuguese
Enable/Disable
0000 to 9999
On/Off
0 to 600
Yes/No
Yes/No
80 to 100
10 to 40
40 to 100
0=No Switch
1=Normal Open
2=Normal Closed
0=No Switch
1=Normal Open
2=Normal Closed
0=No Switch
1=Normal Open
2=Normal Closed
0=No Switch
1=Normal Open
2=Normal Closed
Yes/No
0=No Switch
1=Normal Open
2=Normal Closed
0 to 60
0 to 60
15 to 80
1 to 9.9
120 to 999
300 to 999
120 to 999
0 to 600
Enable/Disable
0 to 100F
Yes//No
45 to 75
0 to 20
--- 20 to 0
35.0 to 65.0
35.0 to 65.0
10 to 50
10 to 50
5 to 50
0 to 50
0 to 500
100 to 500
100 to 500
0 to 100
0 to 100
Software Versions: ___________________________
MBB: CESR131320- -- - _ _
ECB: CESR131249- -- - _ _
MARQ: CESR131171- -- - _ _
Unoccupied: __________________
Unoccupied: __________________
UNITS
DEFAULT
TABLE/SUB--- TABLE
SERVICE
CONFIGURATION
Off
0
Disable
1111
Off
sec
30
Yes
Yes
%
100
%
20
^F
50
0: no FIOP
1: FIOP
0: no FIOP
1: FIOP
0: no FIOP
1: FIOP
0
No
0
mins
0
mins
0
%
70
^F
3
sec
180
sec
300
sec
300
sec
60
Disable: reserved for
future use
DO NOT ENABLE
dF
0
Yes
dF
65
^F
10
^F
--- 10
dF
60
dF
45
dF
18
dF
20
dF
15
dF
10
psig
20
psig
450
psig
200
F
55
F
45
101
CCN
CCN POINT
DISPLAY
DISPUNIT
LANGUAGE
PASS_EBL
PASSWORD
(display only, not in
DISPTEST
table)
UNIT
STARTDLY
OCC_FAN
FATALFAN
SPEEDMAX
SPEEDMIN
SPEEDVNT
FANSTCFG
FILSTCFG
SHTDNCFG
REMOCCFG
RH_OAQ
HUMSTCFG
TCSTCOOL
TCSTHEAT
COOL_CFG
MIN_CAPC
SPEEDDMD
MIN_ON
MIN_OFF
MIN_ON_S
COOL_FOD
A1_SENSE
OATLCOMP
ALM_NOW
SASP
SASPMAXU
SASPMAXD
SATMIN_H
SATMIN_L
SSTOK
SSTLEV1
SSTLEV2
SSTLEV3
DELTAP_A
LEV1MAXP
LEV2MINP
LEV2ON
LEV2OFF
ENTRY