Compressor Operation; Indoor Fan Operation - Carrier 48/50PD05 User Manual

Single package displacement ventilation or single zone variable airflow rooftop units electric cooling/gas heating with puron(r--410a)refrigerant and comfortlink 1.x controls
Table of Contents

Advertisement

(Configuration→CCN→SCH.O→OV.SP) is set to YES.
The length of the override period is determined by the
Timed
Override
(Configuration→CCN→SCH.O→OV>EX).

Compressor Operation

The 48/50 PD units use a Copeland Digital Scroll Compressor that
can vary the refrigerant capacity between 100 and 15%. This is
accomplished by a mechanism in the compressor that separates the
two scroll spirals which stops the pumping of the refrigerant gas.
This mechanism is operated by the differential pressure between
the suction and discharge of the compressor. The pressure to
operate the unloading mechanism is controlled by a small solenoid
situated in a refrigerant line between the top of the compressor and
the suction line. When the solenoid is energized the compressor is
unloaded. The solenoid coil is controlled by the Copeland Digital
Scroll Controller (DSC) that operates on a 1 to 5V signal from the
ComfortLink Auxiliary Board (AUX1) and converts this into a
Pulse Width Modulated (PWM) signal to the solenoid valve. The
pulse width modulated signal is an on and off signal that repeats
every 15 seconds with the off time portion of the 15 seconds
representing the % loading of the compressor.
The Compressor Capacity (Outputs→COOL→CAPC) can be
monitored on the ComfortLink Scrolling Marquee Display. The
Compressor Capacity value is determined by a Proportional,
Integral, Derivative (PID) algorithm that controls the Supply Air
Temperature (Temperatures→AIR.T→SAT) to the Supply Air
Control Point (Run Status→COOL→SA.CP).
The
Compressor
(Configuration→COOL→MIN.C) is configured at the factory to
70%. This is the minimum compressor capacity that gives the
highest SEER rating for a 48 series unit with the highest gas heat
option and no economizer per AHRI standard 210/240. Since the
AHRI rating standard does not account for energy savings that can
be realized by displacement ventilation air distribution system and
extending economizer cooling operation at higher supply air
temperature set points, a complete energy analysis should be
conducted before changing the Compressor Minimum Capacity
(Configuration→COOL→MIN.C) setting to determine the energy
savings
at
a
lower
Compressor
(Configuration→COOL→MIN.C) setting.

Indoor Fan Operation

The indoor fan is controlled by the Indoor Fan VFD Power Relay
(Outputs→FANS→IDF) on the MBB (main base board) control,
which then operates the indoor fan contactor (IFC).
48/50PD
units
the
Indoor
(Outputs→FANS→IDF) is always on so that power is supplied to
the VFD electronic boards.
condensation on the VFD electronic boards and provides power to
the remote VFD display so that error codes and VFD configuration
parameters can be verified.
The 48/50PD unit controls require an accurate supply duct CFM at
the unit design point where the indoor fan will run at the Supply
Fan Maximum Speed (Configuration→UNIT→FS.MX).
Supply Fan Maximum Speed (Configuration→UNIT→FS.MX)
is used for operation of the economizer and power exhaust. The
supply duct CFM is configured by the Indoor Fan Max Speed
CFM (Configuration→ECON→IDF.C).
Indoor Fan Max Speed CFM (Configuration→ECON→IDF.C)
are at 400 CFM per ton or 1600 CFM for the 05 size and 2000
CFM for the 06 size. It is preferred to use the supply duct CFM
from an air balance report to configure the Indoor Fan Max Speed
CFM (Configuration→ECON→IDF.C). If an air balance report
is not available then use the fan tables supplied in this book to
determine
Fan
(Configuration→ECON→IDF.C). When using the fan tables to
determine
Fan
(Configuration→ECON→IDF.C) set Economizer Position Test
Hours
setting
Minimum
Capacity
Minimum
Capacity
On the
Fan
VFD
Power
Relay
This prevents the formation of
The
Default values for
Max
Speed
CFM
Max
Speed
CFM
(Service Test→INDP→ECON) to 0 (Economizer Damper Closed)
and Indoor Fan Speed Test (Service Tes→FANS→F.SPD) equal to
(Configuration→UNIT→FS.MX). Measure the supply to return
duct static pressure difference and indoor fan RPM.
correction to static pressure for all options installed in the unit per
the accessory pressure drop table. Determine Indoor Fan Max
Speed CFM (Configuration→ECON→IDF.C) on the fan table
where the corrected static pressure and RPM cross.
The supply fan speed range is configured by the Supply Fan
Maximum Speed (Configuration→UNIT→FS.MX) and the
Supply Fan Minimum Speed (Configuration→UNIT→FS.MN).
These configuration values are in units of % speed referenced to a
2 to 10VDC signal to the VFD AI1 input with 2VDC representing
0% speed and 10VDC representing 100% speed or 0 to 60HZ
VFD frequency output to the motor.
The
Supply
Fan
(Configuration→UNIT→FS.MN)
between 10 and 70%. The Supply Fan Minimum Speed default
value is 70%, this provides the greatest energy efficiency rating for
a unit without an economizer in a mixed air type duct application.
The
Supply
Fan
(Configuration→UNIT→FS.MX) can be configured between 80
and 100%. The Supply Fan Maximum Speed default value is
100%. Set the indoor fan pulley to the application design point
CFM for heating and cooling at 100% fan speed so that the CFM is
not lower than the minimum CFM allowed in the product data. If
the exact CFM can not be set by the half turn pulley settings then
adjust
the
Supply
(Configuration→UNIT→FS.MX) to fine tune the CFM to the
application requirements.
The Supply Fan Maximum Speed
(Configuration→UNIT→FS.MX) RPM must now produce
supply CFM that is not lower that the minimum CFM allowed in
the product data for heating and cooling.
The indoor fan may operate during cooling with compressors
mode, free cooling with outdoor air mode, heating mode, or for
ventilation with outdoor air mode.
The indoor fan operation can be affected by the following:
S Fan On When Occupied (Configuration→UNIT→OC.FN)
S IAQ Analog Fan Config (Configuration→AIR.Q→IA.FN)
S IAQ Switch Fan Config (Configuration→AIR.Q→II.FN)
S Fan Status Switch (Configuration→UNIT→FN.SW)
When the unit is in occupied or unoccupied cooling mode the
supply fan will modulate to maintain the space temperature sensor
set point between the configured Supply Fan Maximum Speed
(Configuration→UNIT→FS.MX) and the Supply Fan Minimum
Speed (Configuration→UNIT→FS.MN).
When the 40PD or 50 PD unit is in occupied or unoccupied
heating mode (gas heat or electric heat mode) the indoor fan will
operate
at
the
Supply
(Configuration→UNIT→FS.MX) setting.
For 48PD gas heating units, the IGC control fan output is also
monitored by the MBB control. This can result in additional
modifications of fan delays or other operation due to safety
functions of the IGC control.
When the PD unit is in free cooling mode the indoor fan will
modulate
to
maintain
The
(Setpoints→OCSP),
the
Unoccupied
(Setpoints→UCSP),
Occupied
(Setpoints→OHSP),
or the
(Setpoints→UHSP).
When the PD unit is in ventilation mode and Fan On When
Occupied (Configuration→UNIT→OC.FN) the indoor fan will
operate
at
the
Vent
(Configuration→UNIT→FS.VM).
(Configuration→UNIT→FS.VM) factory default is 50% and can
be user configured between 40 and 100%.
14
Make
Minimum
Speed
can
be
user
configured
Maximum
Speed
Fan
Maximum
Speed
Fan
Maximum
Speed
Occupied
Cool
Set
Point
Cool
Set
Point
Heat
Set
Point
Unoccupied
Heat
Set Point
Mode
Fan
Speed
Vent Mode Fan Speed

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48pd0548pd0650pd0550pd06

Table of Contents