Connections on the heating water side
2. Connect the hydraulic lines.
System with 1 heating circuit:
Connect the heating return to boiler return 1.
System with 2 heating circuits:
Connect the heating circuit with the higher tem-
perature level to boiler return 2.
Boiler return 1 must be connected and receive a
flow equal to at least 15 % of the rated heating
output.
!
Please note
Mechanically loaded hydraulic connections
lead to leaks, vibrations and appliance dam-
age.
Connect on-site lines so that they are free of
load and torque stress.

Fitting the thermal insulation

3.
8x
Fig. 11
Black side should face outwards
A
Note
If required, secure the spring hooks to the boiler base.
8x
A
4.
(cont.)
3. Seal any unused connections.
Note
Never connect a heat consumer to connector
(safety connection).
4. Check the hydraulic connections for tightness.
!
Please note
Unsuitable water quality can damage the
boiler body.
Only fill the boiler with water that complies
with the "Water quality requirements": See
"Vitocrossal, type CRU" service instructions
5. Thermally insulate the hydraulic lines.
2.
1.
4x
D
17