Viessmann VITOFLAME 100 Service Instructions Manual page 9

Table of Contents

Advertisement

Further details regarding the individual steps
7. If required, adjust the oil
pressure at pressure adjusting
screw C for stage 1 and D for
stage 2.
Clockwise
Anti−clockwise ³ pressure falls.
For standard burner settings,
see page 38.
8. Check the emission values by
taking an actual measurement
after adjusting the oil pressure.
9. Switch OFF the mains isolator
and safeguard against
unauthorised reconnection.
10. Remove the pressure and
vacuum gauges.
11. Insert plug "P" A and "V" B.
Check the plug seals for damage
and replace, if required.
12. Start the burner and check the
plugs for leaks.
Initial start−up, inspection and maintenance
³ pressure rises
(cont.)
9