Combustion Test Target Ranges
Figure:
Gas valve and fan
The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in 
the field unless indicated   i n these instructions. 
After converting the appliance to propane, a combustion (CO
using properly functioning and calibrated combustion analyzing equipment and the results compared to the values 
in Table 1.
Propane
Max. CO
 value
2
Min. CO
 value
2
Table 1
- Propane CO
values at High and Low Fire
2
2 |
CO
Value (%) at High Fire with front
2
cover open
11.5%
9.8%
) reading must be taken by a qualified technician 
2
CO
Value (%) at Low Fire with front
2
cover open
Actual Value at High Fire Minus - 0.3%
9.5%