Table 12 — LID Primary and Secondary Messages and Custom Alarm/Alert Messages
L. CHILLER PROTECT LIMIT FAULTS (cont)
Excessive numbers of the same fault can lead to severe chiller
damage. Seek service expertise.
PRIMARY MESSAGE
SECONDARY MESSAGE
PROTECTIVE LIMIT
TRANSDUCER VOLTAGE FAULT
PROTECTIVE LIMIT
LOW GEAR OIL PRESSURE
PROTECTIVE LIMIT
HIGH GEAR OIL TEMP
PROTECTIVE LIMIT
CCN OVERRIDE STOP
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by
the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage,
etc., at which the control tripped. [OPEN] indicates that an input circuit is open.
M. CHILLER ALERTS
PRIMARY MESSAGE
RECYCLE ALERT
SENSOR FAULT ALERT
SENSOR FAULT ALERT
LOW OIL PRESSURE
ALERT
AUTORESTART PENDING
AUTORESTART PENDING
AUTORESTART PENDING
SENSOR ALERT
SENSOR ALERT
CONDENSER PRESSURE
ALERT
RECYCLE ALERT
SENSOR ALERT
SENSOR ALERT
*[LIMIT] is shown on the LID as the temperature, pressure, voltage, etc., set point predefined or selected by
the operator as an override, alert, or alarm condition. [VALUE] is the actual temperature, pressure, voltage,
etc., at which the control tripped.
with Troubleshooting Guides (cont)
ALARM MESSAGE/PRIMARY CAUSE
V
Check transducer power supply.
GEAROILP [VALUE] exceeded imit of
[LIMIT]*. Check gear oil pump filter.
GEAOILT [VALUE] exceeded limit of
[LIMIT]*. Check gear oil cooler filter.
CHIL
local run mode.
SECONDARY MESSAGE
HIGH AMPS AT SHUTDOWN
LEAVING COND WATER TEMP
ENTERING COND WATER TEMP
CHECK OIL FILTER
POWER LOSS
LOW LINE VOLTAGE
HIGH LINE VOLTAGE
HIGH DISCHARGE TEMP
HIGH BEARING TEMP
PUMP RELAY ENERGIZED
EXCESSIVE RECYCLE STARTS
LOW GEAR OIL PRESSURE
HIGH GEAR OIL TEMP
REF [VALUE] exceeded limit of [LIMIT]*.
S
S CCN. Override stop while in
ALARM MESSAGE/PRIMARY CAUSE
High Amps at Recycle: Check guide vane
drive.
Sensor Fault: Check leaving condenser
water sensor.
Sensor Fault: Check entering condenser
water sensor.
Low Oil Pressure Alert: Check oil
V
P Power Loss: Check voltage
supply.
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
V
P [VALUE] exceeded limit of [LIMIT]*.
Check voltage supply.
CMPD [VALUE] exceeded limit of
[LIMIT]*. Check discharge
temperature.
MTRB [VALUE] exceeded limit of
[LIMIT]*. Check thrust bearing
temperature.
CRP High Condenser Pressure [LIMIT]*.
Pump energized to reduce pressure.
Excessive recycle starts.
GEAROILP [VALUE] exceeded imit of
[LIMIT]*. Check gear oil pump filter.
GEAOILT [VALUE] exceeded limit of
[LIMIT]*. Check gear oil cooler filter.
91
ADDITIONAL CAUSE/REMEDY
Check transformer power (5 vdc) supply to
transducers. Power must be 4.5 to 5.5 vdc.
Check for closed oil supply valves. Check oil fil-
ter. Check transducer accuracy.
Check for cooler water flow. Check sensor for
accuracy.
Machine received a command from the net-
work to stop overriding local operating mode.
ADDITIONAL CAUSE/REMEDY
Check that guide vanes are closing. Check
motor amps correction calibration is cor-
rect. Check actuator for proper operation.
Check sensor. See sensor test procedure.
Check oil filter. Check for improper oil level
or temperature.
Check power supply if there are excessive
compressor starts occurring.
Discharge temperature exceeded the alert
threshold. Check entering condenser water
temperature.
Thrust bearing temperature exceeded the
alert threshold. Check for closed valves, im-
proper oil level or temperatures.
Check ambient conditions. Check con-
denser pressure for accuracy.
The chiller load is too small to keep the chiller
on line and there have been more than 5
restarts in 4 hours. Increase chiller load, ad-
just hot gas bypass, increase RECYCLE RE-
START DELTA T from SERVICE1 screen.
Check for closed oil supply valves. Check
oil filter. Check transducer accuracy.
Check for cooler water flow. Check sensor
for accuracy.